Description
Basic Hardware Information
‑ Connector form: 25‑pin female D‑Sub connector, internal integrated precision termination resistor pack ‑ Supported expansion cables: IC693CBL302, IC693CBL314 ‑ Maximum total expansion cable length: 15 m (50 ft) ‑ Power consumption: Passive device, no external power supply required ‑ Mechanical: Compact D‑Sub plug‑in housing; weight approx 0.05‑0.14 kg; no DIN‑rail mounting required; directly plug into baseplate expansion port; non‑hot‑swappable, perform plug‑unplug under rack power‑off condition ‑ Operating ambient temperature: 0 ℃ ~ +60 ℃; storage temperature ‑40 ℃ ~ +85 ℃; relative humidity 5‑95 % non‑condensing ‑ Safety certification: UL, cUL, CE ‑ Handling note: ESD‑sensitive component; anti‑static wrist strap required during handling ‑ Compatibility: Only for Series 90‑30 PLC expansion‑I/O bus; cannot apply to Genius bus or Series 90‑70 expansion interface. Only one terminator shall exist within one expansion chain, install on final rack only.
Core Functions & Features
- Provides correct impedance termination for Series 90‑30 parallel expansion‑I/O bus, eliminates high‑speed signal reflection and ringing on multi‑rack daisy‑chain expansion topology, guarantees stable data transmission between CPU and remote expansion baseplates。
- Passive hardware device, no configuration software setting needed; physical plug‑in completes termination function.
- Restricts signal‑reflection‑induced faults: intermittent expansion‑rack offline, random module fault reporting, PLC scan time overtime, sporadic I/O data distortion.
- Revision‑A unit is drop‑in replacement for base IC693ACC307; no modification for wiring and system structure.
On‑site Installation & Commissioning Notes
- Cut off whole PLC rack power before plugging or removing IC693ACC307; apply anti‑static protection.
- In multi‑rack expansion daisy‑chain system, install this terminator only on the expansion D‑Sub port of the last expansion baseplate. Do not install on CPU main‑rack port or intermediate‑rack port; multiple terminators on same chain will cause bus communication failure。
- Tighten D‑Sub fixing screws to prevent vibration‑induced loose contact. Arrange expansion‑cable routing separately from high‑voltage power cables to reduce EMI interference.
- After completing whole expansion‑chain wiring and terminator installation, power‑on PLC, verify all expansion‑rack modules are fully recognized inside programming software, check for expansion‑bus fault bits.
- Replacement note: Generic third‑party D‑Sub plug cannot substitute for IC693ACC307, internal resistor network is mandatory. After replacement, double‑check installation position (last rack only), and perform full‑point I/O validation test.
Common On‑site Abnormal Conditions
‑ Intermittent expansion‑rack drop‑out: Missing terminator plug; terminator installed on intermediate rack; loose D‑Sub connector; damaged internal resistor inside terminator. ‑ Some expansion‑I/O modules cannot be recognized: Wrong terminator position, damaged expansion cable, D‑Sub connector pin damage on baseplate. ‑ Sporadic I/O data jitter / random module fault alarms: Signal reflection caused by missing or defective terminator, heavy EMI interference on expansion‑cable route. ‑ Whole expansion‑chain no communication: Two terminators fitted on same expansion chain simultaneously. ‑ Terminator physical damage: Surge voltage conducted through expansion cable, ESD impact on D‑Sub interface.