Description
Hardware & Electrical Specifications
‑ Model:IC693ALG223D ‑ Part Number:IC693ALG223D ‑ Module Type:Series‑90‑30 16‑Channel Single‑Ended Analog Current Input Module ‑ Mounting:Plug‑in onto Series‑90‑30 PLC backplane slot ‑ Backplane power:5 VDC @120 mA drawn from PLC rack backplane ‑ Field loop power:External 18‑30 VDC nominal 24 VDC; minimum 65 mA for field transmitter loop supply ‑ Input channels:16 single‑ended analog current inputs, common ground group ‑ Configurable signal ranges: • 0‑20 mA • 4‑20 mA (factory default) • 4‑20 mA Enhanced (open‑wire fault detection enabled) ‑ Resolution:12‑bit; 4 μA typical @4‑20 mA range ‑ Input impedance:250 Ω per channel ‑ Typical update time:6 ms full‑module scan cycle ‑ Built‑in filter:200 Hz cutoff frequency ‑ Isolation:250 VAC continuous; 1500 VAC 1‑minute withstand between field side and PLC logic backplane; no channel‑to‑channel isolation inside group ‑ Diagnosis:Per‑channel over‑range / under‑range alarm; open‑wire detection under Enhanced‑4‑20mA mode; module power‑failure status reporting to CPU ‑ Terminal:Removable screw‑clamp terminal block ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:Field‑loop transient surge suppression, module self‑diagnostic circuit ‑ Compatibility note:Cannot work standalone; must install in Series‑90‑30 PLC base rack; full analog‑loop simulation test mandatory after replacement。
Environmental Specifications
‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight:approx 0.43 kg ‑ Dimension:Series‑90‑30 standard single‑slot module form‑factor ‑ Handling note:ESD‑sensitive precision analog circuit, anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Collect process current signals from field 2‑wire /4‑wire pressure, flow, level and temperature transmitters.
- Software configurable per‑channel range; Enhanced mode detects broken transmitter wiring for field troubleshooting.
- Convert analog current signals to 12‑bit digital data, communicate with Series‑90‑30 CPU via backplane bus.
- Channel‑level fault diagnostics: over‑range, under‑range and open‑loop fault, upload alarm status to PLC CPU.
- LED status indication: ‑ Green OK:Module power‑on and self‑test pass
Installation & Wiring Requirements
- Cut off Series‑90‑30 PLC rack power and external 24VDC field‑loop power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling module.
- Insert IC693ALG223D fully into PLC backplane slot and lock latch.
- Field instrument wiring strictly follow GE Series‑90‑30 hardware manual; adopt shielded twisted‑pair instrument cable; separate analog signal cables from high‑power cables, connect shielding to dedicated protective ground terminal.
- Complete protective grounding according to GE system specification.
- After replacement: power‑on PLC, verify OK LED status, download module channel configuration, perform full‑channel signal test and open‑wire fault‑simulation test.
- Replacement note: Verify CPU firmware compatibility; full analog‑loop simulation test mandatory before unit put‑into‑service.