Description
Basic Hardware Information
‑ Output channels: 2 independent single‑ended voltage outputs ‑ Output range:‑10 VDC ~ +10 VDC bipolar ‑ DAC resolution: 13‑bit (12‑bit + sign); step size 2.5 mV ‑ Update time: 5 ms typical for both channels ‑ Accuracy: ±5 mV @25 ℃; ±15 mV over full operating temperature range ‑ Minimum load resistance: 2 kΩ per channel; max load capacitance 2000 pF ‑ Galvanic isolation: 1500 V RMS 1‑minute dielectric withstand between field circuit and PLC logic backplane; no channel‑to‑channel isolation ‑ Power consumption: 40 mA @5 VDC (backplane logic); 100 mA @24 VDC external user power ‑ Termination: Detachable screw terminal block ‑ Mechanical: Single‑slot Series 90‑30 form‑factor; baseplate mounting; non‑hot‑swappable, rack power must be removed during module replacement ‑ Status indicators: Front‑panel OK LED for module health status ‑ Operating ambient temperature: 0 ℃ ~ +60 ℃; storage temperature ‑40 ℃ ~ +85 ℃; relative humidity 5‑95 % non‑condensing ‑ Handling note: ESD‑sensitive hardware; anti‑static wrist strap required during maintenance ‑ Compatibility: Works with Series 90‑30 CPU family; cannot be used in Series 90‑70 / VersaMax racks.
Core Functions & Features
- Converts digital values stored in PLC %AQ registers into‑10 ~ +10 VDC analog control signals, regulating control valves, actuator positioners and variable‑speed drive set‑points.
- Bipolar output supports positive‑negative control requirements for forward/reverse adjustment scenarios.
- Channel‑level short‑circuit protection; output shuts down under short‑circuit condition to avoid internal driver damage.
- Detachable terminal block keeps field wiring intact while swapping module, shortens maintenance downtime.
- Revision‑F /‑G units are direct drop‑in replacements for older IC693ALG390 hardware; no wiring or software modification required.
On‑site Installation & Commissioning Notes
- Power‑off complete Series 90‑30 rack before installing or removing IC693ALG390; apply anti‑static protection. Fully seat module into baseplate slot until locking tab clicks firmly.
- Use shielded twisted‑pair cables for analog field wiring; separate analog signal cables from high‑voltage AC and heavy‑power discrete wiring to reduce EMI interference; single‑point shield grounding is recommended. Torque terminal‑block screws to specified torque value.
- Provide stable 24 VDC external user power supply to module terminals; verify power polarity to prevent driver damage.
- Complete hardware slot configuration within PLC programming software, assign slot module‑type as IC693ALG390, download configuration to CPU.
- After commissioning, verify steady‑on OK‑LED status. Perform signal output test for each channel, validate output voltage range and response performance.
- Replacement note: Current‑output analog modules cannot serve as direct substitute. After replacement, confirm external 24 VDC user‑supply and execute full‑point analog‑channel test.