Description
Basic Hardware Information
‑ Output channels: 2 single‑ended current‑only analog outputs ‑ Output range: Hardware jumper selectable 0‑20 mA / 4‑20 mA per channel ‑ DAC resolution: 12‑bit; step size 4 μA (4‑20 mA), 5 μA (0‑20 mA) ‑ Full‑channel update time: 5 ms typical for both channels ‑ Accuracy: ±0.1 % full‑scale @25 ℃; ±0.25 % full‑scale across full operating‑temperature range ‑ Maximum loop load resistance: 850 Ω per channel ‑ Short‑circuit protection: Built‑in per‑channel hardware short‑circuit shutdown protection ‑ Galvanic isolation: 1500 V RMS 1‑minute dielectric withstand between field analog circuits and PLC logic backplane; no channel‑to‑channel isolation ‑ Power consumption: 30 mA @5 VDC backplane logic power; 215 mA @24 VDC external isolated field‑side power ‑ Termination: Detachable screw‑type terminal block ‑ Mechanical: Single‑slot Series 90‑30 form‑factor, baseplate mounting; non‑hot‑swappable, rack main power must be removed for module replacement ‑ Status indicators: Front‑panel OK LED for module health status ‑ Operating ambient temperature: 0 ℃ ~ +60 ℃; storage temperature ‑40 ℃ ~ +85 ℃; relative humidity 5‑95 % non‑condensing ‑ Handling note: ESD‑sensitive hardware; anti‑static wrist‑strap required during maintenance ‑ Compatibility: Works with Series 90‑30 CPU family; incompatible with Series 90‑70 and VersaMax racks.
Core Functions & Features
- Converts digital values stored in PLC %AQ analog‑output registers into industry‑standard 0‑20 mA /4‑20 mA loop‑current signals for proportional valves, positioners and analog actuator set‑point control.
- Terminal‑block jumpers independently set current‑range for each channel, supporting mixed‑range field‑device requirements.
- Per‑channel self‑reset short‑circuit hardware protection; cuts off output drive under short‑circuit fault to avoid internal driver damage.
- Detachable terminal‑block design keeps field wiring intact while swapping module, shortens maintenance downtime.
- Revision‑F /‑G units are direct drop‑in replacements for older IC693ALG391 hardware; no wiring or software modification required after replacement.
On‑site Installation & Commissioning Notes
- Power‑off complete Series 90‑30 rack before installing or removing IC693ALG391; apply anti‑static protection. Fully seat module into baseplate slot until locking tab clicks firmly into place.
- Use shielded twisted‑pair cables for analog field wiring; separate analog signal cables from high‑voltage AC and heavy‑power discrete wiring to reduce EMI interference; single‑point shield grounding is recommended. Torque terminal‑block screws to specified torque value.
- Configure terminal‑block jumpers to match actual field‑device current‑range requirements. Supply stable 24 VDC external isolated power to module terminals and verify correct polarity.
- Complete hardware slot configuration within PLC programming software, assign slot module‑type as IC693ALG391, download configuration to CPU.
- After commissioning, verify steady‑on OK‑LED status. Perform output‑signal test for each channel, validate current‑output range and response performance; simulate short‑circuit condition to verify protective‑shutdown function.
- Replacement note: Voltage‑output analog modules such as IC693ALG390 cannot serve as direct substitute. After replacement, double‑check jumper‑range settings and external 24 VDC power‑supply, execute full‑point analog‑channel test.
Common On‑site Abnormal Conditions
‑ Module OK‑LED off after power‑on: Poor module seating on baseplate socket, baseplate backplane power abnormality, missing / reversed external 24 VDC field‑side power, internal module hardware failure. ‑ Zero output on both channels: Loss of external 24 VDC drive‑power, incorrect hardware‑configuration download. ‑ Single‑channel no output: Field‑side short‑circuit triggering channel‑protection shutdown, loose terminal‑block screw contact, internal DAC‑driver damage. ‑ Output saturated high/low: %AQ register value out of valid range, actual loop load resistance exceeds maximum 850 Ω specification. ‑ Analog output drift / offset: Cabinet ambient‑temperature exceeds rated operating range, heavy electromagnetic‑interference. ‑ Intermittent output deviation: Vibration‑induced loose terminal‑block contact, unstable external 24 VDC power‑supply.