Description
Hardware & Electrical Specifications
‑ Model:IC693BEM331 ‑ Part Number:IC693BEM331 ‑ Module Type:Series‑90‑30 Genius Bus Master Module ‑ Mounting:Plug‑in onto Series‑90‑30 PLC backplane I/O slot ‑ Backplane power:5 VDC @ 650 mA drawn from rack backplane ‑ Genius bus capacity:max 30 slave nodes per module ‑ Supported baud‑rate:38.4k /76.8k /153.6 k standard /153.6 k extended baud‑rate ‑ Communication services:Global‑Data cyclic broadcast, Datagram acyclic message, Directed Control Data, slave fault reporting ‑ Genius‑bus interface:Screw terminal block on module front for shielded twisted‑pair bus cable ‑ Buffer memory:On‑board dual‑port RAM for data exchange between Genius bus and PLC CPU ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:Bus transient surge suppression, hardware watchdog, comprehensive bus‑error statistic counters ‑ Compatibility note:Cannot run standalone; must work with Series‑90‑30 CPU; baud‑rate must match all Genius slave nodes; terminating resistors required at both physical ends of copper bus trunk; full Genius‑bus simulation test mandatory after replacement。
Environmental Specifications
‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight:approx 0.39 kg ‑ Dimension:Series‑90‑30 standard single‑slot module form‑factor ‑ Handling note:ESD‑sensitive communication circuit, anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Serve as Genius‑bus master for Series‑90‑30 PLC, manage bus token passing, schedule cyclic data communication for all Genius remote I/O slaves.
- Realize bidirectional data exchange between Series‑90‑30 CPU and Genius distributed I/O blocks, process global‑data, datagram messages and diagnostic information.
- Collect bus error counters and slave block fault status, report diagnostic alarms to PLC CPU.
- LED status indication: ‑ Green OK:Module power‑on and self‑test pass ‑ COM:Genius‑bus communication activity indicator ‑ FAULT:Bus error / slave fault alarm
Installation & Wiring Requirements
- Cut off Series‑90‑30 PLC rack power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling module.
- Insert IC693BEM331 fully into PLC backplane slot and lock latch.
- Genius‑bus wiring strictly follow GE Genius hardware manual; use shielded twisted‑pair bus cable; install terminating resistor at both physical ends of bus trunk; separate bus cables from high‑power cables, connect shielding to dedicated protective ground terminal.
- Complete protective grounding according to GE system specification.
- After replacement:power‑on PLC, verify OK / COM / FAULT LED status, download Genius hardware configuration, perform bus‑scan and full I/O‑loop commissioning test.
- Replacement note: Verify CPU firmware compatibility; confirm baud‑rate consistent with all slave devices; full Genius‑bus‑loop simulation test mandatory before unit put‑into‑service.