GE IC693CMM321 Series 90‑30 TCP/IP Ethernet Communications Module

IC693CMM321 is independent Ethernet communication processor module for GE Fanuc Series‑90‑30 PLC. It occupies one backplane slot, integrates self‑contained TCP/IP protocol stack, offloads all Ethernet communication processing from PLC main CPU. It supports SRTP (Serial Real‑Time Protocol) and Modbus TCP master/slave, realizes data exchange between PLC, HMI, upper computer and other third‑party Ethernet devices. Configured via Proficy Machine Edition software, supports firmware upgrade. It is widely used for factory network monitoring and inter‑PLC communication. Product status: Obsolete, spare‑part only supply available。

Email:2306444920@qq.com
Phone:+86 17759635229

Description

Hardware & Electrical Specifications

‑ Model:IC693CMM321 ‑ Part Number:IC693CMM321 ‑ Module Type:Series‑90‑30 TCP/IP Ethernet Communication Processor Module ‑ Mounting:Plug‑in onto Series‑90‑30 PLC backplane arbitrary I/O slot ‑ Backplane power:5 VDC @450 mA drawn from rack backplane ‑ Ethernet interface:1×RJ45, 10 Mbps 10Base‑T ‑ Supported protocols:SRTP server/client, Modbus‑TCP master/slave ‑ Max concurrent TCP connections:8 connections ‑ Modbus‑TCP default port:502 ‑ Station manager port:RJ‑11 RS‑232 serial debugging port for local IP address setting ‑ On‑board memory:64KB dual‑port RAM for backplane‑Ethernet data buffer ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:Hardware watchdog, network fault statistics, surge suppression ‑ Compatibility note:Cannot run standalone; match Series‑90‑30 CPU; firmware version shall match project configuration; full network communication test mandatory after replacement。

Environmental Specifications

‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification

Mechanical Data

‑ Weight:approx 0.32 kg ‑ Dimension:Series‑90‑30 standard single‑slot module form‑factor ‑ Handling note:ESD‑sensitive network circuit, anti‑static wrist‑strap mandatory during handling

Main Functions

  1. Independent TCP/IP Ethernet co‑processor, undertake Ethernet communication tasks without occupying PLC CPU scan resources.
  2. SRTP protocol: realize data read‑write between PLC and HMI, programming software, inter‑PLC data exchange.
  3. Modbus‑TCP master/slave function: realize interconnection with third‑party Modbus‑TCP instruments, drives and upper monitoring system.
  4. RJ‑11 debug port: local setting of IP address, subnet mask, gateway without Ethernet network.
  5. LED status indication:   ‑ Green OK:Module power‑on and self‑test pass   ‑ LAN:Ethernet physical link status indicator   ‑ TX/RX:Network data sending/receiving activity indicator   ‑ FAULT:Module hardware / network communication fault alarm

Installation & Wiring Requirements

  1. Cut off Series‑90‑30 PLC rack power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling module.
  2. Insert IC693CMM321 fully into PLC backplane slot and lock latch.
  3. Use industrial shielded Ethernet cable for network wiring; separate network cables from high‑power cables; comply with industrial network wiring specification.
  4. Complete protective grounding according to GE hardware manual.
  5. After replacement: power‑on PLC, verify OK / LAN / FAULT LED status; set IP parameter via station‑manager port or software; download module configuration; perform Modbus‑TCP and SRTP communication test.
  6. Replacement note: Verify CPU firmware compatibility; pay attention to network isolation, the module has no built‑in network encryption authentication; full system communication commissioning test mandatory before unit put‑into‑service。

Reviews

There are no reviews yet.

Be the first to review “GE IC693CMM321 Series 90‑30 TCP/IP Ethernet Communications Module”

Your email address will not be published. Required fields are marked *