GE IC693CPU313 Embedded 5‑Slot Turbo CPU Baseplate

Series 90‑30 compact integrated CPU rack, CPU embedded on 5‑slot backplane, small‑scale standalone PLC controller, no external CPU plug‑in module, no multi‑rack expansion capability。

Email:2306444920@qq.com
Phone:+86 17759635229

Description

Basic Hardware Information

‑ Processor: Intel 80188 Turbo, 10 MHz ‑ Logic scan speed: 0.6 ms / 1K Boolean contacts ‑ User program memory: 12 KB ‑ Register memory (%R): 1024 words ‑ Max discrete I/O: 160 total (%I+%Q combined) ‑ Analog capacity: 64 AI words, 32 AQ words ‑ Internal memory resources: %G 1280 bits, %M 1024 bits, %T 256 bits, %S 128 system status bits ‑ Slots: 5‑slot baseplate; slot‑0 = dedicated power‑supply slot; slots 1‑5 for I/O / communication modules ‑ Expansion capability: No expansion bus interface, multi‑rack expansion not supported ‑ On‑board communication: RS‑485 SNP/SNP‑X slave port (via power‑supply connector) ‑ Real‑time clock: None ‑ Back‑plane consumption: 430 mA @5 VDC ‑ Mechanical: DIN‑rail mount integrated base‑plate assembly; weight approx 1.8‑2.0 kg ‑ Protection rating: IP20 (cabinet‑only installation) ‑ Operating ambient temperature: 0 ℃ ~ +60 ℃; storage temperature‑40 ℃ ~ +85 ℃; relative humidity 5‑95 % non‑condensing ‑ Handling note: ESD‑sensitive integrated PCB; anti‑static wrist‑strap required during module replacement; program loss risk when power‑supply battery is exhausted ‑ Compatibility: Series 90‑30 I/O and communication modules; cannot work with expansion baseplates IC693CHS392 / IC693CHS398; incompatible with Series 90‑70 / RX3i hardware.

Core Functions & Features

  1. Integrated PLC controller executing user ladder logic, handles discrete/analog I/O processing, timer‑counter arithmetic and user logic operations for small‑scale standalone equipment.
  2. RS‑485 SNP‑X slave interface supports programming software download/upload, connects to third‑party HMI/SCADA via SNP protocol.
  3. Supports standard Series 90‑30 I/O and intelligent communication modules (CMM, BEM series) within local 5‑slot chassis; total back‑plane current budget must be observed.
  4. Memory backup: power‑supply battery maintains register data; super‑capacitor preserves data for limited hours after power‑supply removal; long‑term power‑off results in register data loss, program stored in non‑volatile EPROM remains intact。
  5. No expansion‑bus hardware; system I/O capacity strictly limited to local 5‑slot rack resources.
  6. Different hardware‑firmware revisions are mechanical‑electrical drop‑in replacements; after replacement, re‑download PLC project and hardware configuration.

On‑site Installation & Commissioning Notes

  1. Power‑off the system before inserting or removing modules. Secure base‑plate firmly on cabinet DIN‑rail.
  2. Install matching Series 90‑30 power‑supply into far‑left slot, populate I/O / communication modules into slots 1‑5, press modules fully until locking tab clicks. Check total 5 VDC current consumption does not exceed power‑supply rating.
  3. RS‑485 SNP communication wiring: connect programming cable to power‑supply serial port; use shielded twisted‑pair, terminate bus ends.
  4. Download ladder program and hardware configuration via programming software; verify CPU RUN status, monitor system status bits (%S).
  5. Periodically inspect power‑supply backup‑battery aging; battery failure will lose register data on power‑loss, user program is preserved.
  6. Replacement note: Cannot substitute with discrete CPU‑module plus separate CHS main‑baseplate. After replacement, re‑download project, verify I/O channels and serial SNP communication.