Hardware Specifications
- Processor: Intel 80386EX, 25 MHz, firmware‑supported floating‑point math
- User Memory: 240 KB configurable RAM / Flash memoryMoore Auto…
- I/O Capacity: Max 2048 discrete inputs / 2048 discrete outputs; up to 32640 analog words
- Scan Speed: ~0.22 ms per 1K boolean logic contactsMoore Auto…
- Communication: Built‑in 10Base‑T Ethernet; power‑supply‑mounted SNP/SNPX slave serial port; Genius bus compatible
- Power Draw: 5 VDC, 1100 mA, single‑slot backplane installationMoore Auto…
- Operating Temperature: 0 °C ~ 60 °C
- Expansion: 1 main baseplate plus up to 7 expansion / remote I/O baseplates (total 8 racks)Moore Auto…
- Programming Software: Proficy Machine Edition, VersaPro
Core Functions
- Execute ladder‑logic and function‑block programs with watchdog fault supervision.
- Support PID control, high‑speed counter, timer‑counter, shift‑register and periodic interrupt subroutines.
- Ethernet for program download, HMI connection and peer‑to‑peer PLC data exchange.
- Native Genius bus interface for distributed Genius I/O network deployment.
- On‑board system diagnostics, fault logging, battery‑backed RAM for program and data retention during power loss.
Installation Requirements
- Insert into dedicated CPU slot of Series 90‑30 main baseplate.
- Verify rack power‑supply can deliver sufficient 5 VDC current for CPU and other modules.
- Install IC693ACC302 lithium backup‑battery module to preserve data on power‑off.
- Operate within 0‑60℃ ambient, avoid heavy dust, vibration and condensation.
- Complete hardware configuration before downloading user application program.
Common Fault Modes
- CPU fault LED active: watchdog timeout, program execution fault, memory parity error, fatal configuration mismatch.
- Unable to enter RUN mode: missing program, hardware configuration mismatch, key‑switch set to STOP state.
- Ethernet communication failure: cable defect, wrong IP address setting, firmware incompatibility with partner devices.
- Data loss after power cycle: backup‑battery low voltage or defective unit.
- Real‑time clock failure: backup‑battery exhaustion, battery replacement required.