GE IC693CPU374 Series 90‑30 High‑Performance Built‑in Dual‑Port Ethernet CPU Module

IC693CPU374 is top‑grade CPU for GE Fanuc Series‑90‑30 PLC platform, single‑slot design, adopts 133MHz embedded 586 processor, integrates built‑in dual‑port 10/100M Ethernet switch, no need for additional CMM321 communication module. Supports SRTP, EGD Ethernet global data, Modbus‑TCP master/slave protocol. Equipped with 240KB configurable user flash‑RAM memory, hardware floating‑point arithmetic, periodic interrupt subroutine, EZ store offline program download function. Serial SNP‑X communication depends on RS‑485 interface on power supply module. Programming software: Proficy Machine Edition / VersaPro. Product status: Obsolete, spare‑part only supply available。

Email:2306444920@qq.com
Phone:+86 17759635229

Description

Hardware & Electrical Specifications

‑ Model:IC693CPU374 ‑ Part Number:IC693CPU374 ‑ Module Type:Series‑90‑30 High‑Performance Dual‑Port On‑Board Ethernet CPU Module ‑ Mounting:Dedicated CPU slot on Series‑90‑30 main baseplate ‑ Processor:Embedded 586, 133 MHz ‑ Backplane power:5 VDC @1480 mA, power consumption 7.4W, high‑capacity power supply recommended ‑ Logic execution speed:0.15 ms / 1K Boolean logic instruction ‑ User program memory:240 KB configurable Flash/RAM, program can be stored in flash memory ‑ I/O capacity:  • Discrete input %I:2048 points  • Discrete output %Q:2048 points  • Analog input %AI:max 32640 words  • Analog output %AQ:max 32640 words  • Register %R:128‑32640 configurable words  • Timers/Counters:>2000 sets (depends on memory) ‑ Rack expansion:Max 8 racks total (1 CPU base +7 expansion racks) ‑ Communication interfaces:  • Dual RJ45 10/100Mbps Ethernet with built‑in switch, support daisy‑chain network wiring  • No onboard serial port; SNP‑X RS‑485 port located on power‑supply module ‑ Supported Ethernet protocols:SRTP server/client, EGD Ethernet Global Data, Modbus‑TCP master/slave ‑ Memory backup:RTC clock & RAM data backed up by power‑supply internal battery; external battery IC693ACC302 extends backup time to 15 months ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:Hardware watchdog timer, comprehensive system self‑diagnosis, power‑fail detection ‑ Compatibility note:Cannot run standalone; must install in dedicated CPU slot of Series‑90‑30 baseplate; high‑capacity power supply is recommended; full system download & I/O verification test mandatory after replacement。

Environmental Specifications

‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification

Mechanical Data

‑ Weight:approx 0.40 kg ‑ Dimension:Series‑90‑30 standard single‑slot CPU module form‑factor ‑ Handling note:ESD‑sensitive high‑speed logic circuit, anti‑static wrist‑strap mandatory during handling; pay attention to backup‑battery status during maintenance

Main Functions

  1. Execute ladder logic, function block, structured‑text user program; hardware floating‑point arithmetic, periodic interrupt subroutine processing.
  2. Dual‑port integrated Ethernet switch, realize PLC programming download, HMI connection, EGD inter‑PLC data exchange, Modbus‑TCP third‑party device communication, support network daisy‑chain wiring, save network switch hardware.
  3. Manage backplane bus, realize data exchange with local I/O, special‑function modules and multi‑expansion racks.
  4. System‑level fault diagnosis: power failure, program error, I/O fault, watchdog overtime; store fault log; support EZ‑Store offline program download without PC.
  5. LED status indication on front panel:   ‑ Green RUN:CPU run mode indicator   ‑ Red FAULT:CPU hardware / program fault alarm   ‑ Green OK:Power‑on and self‑test pass indicator   ‑ LAN1 / LAN2:Ethernet link / activity indicator

Installation & Wiring Requirements

  1. Cut off full PLC rack power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling CPU module.
  2. Insert IC693CPU374 into dedicated CPU slot on main baseplate and lock latch; check power‑supply backup‑battery condition.
  3. If using expansion racks, connect official GE expansion cable between main‑base and expansion‑base 25‑pin D‑sub port.
  4. Use industrial shielded Ethernet cable for network wiring; separate network cables from high‑power cables; complete protective grounding according to GE Series‑90‑30 hardware manual specification.
  5. After replacement:power‑on PLC, verify RUN / OK / FAULT / LAN LED status; set IP address, download hardware configuration & user program; perform full local & expansion‑rack I/O test and Ethernet communication test.
  6. Replacement note: Verify project firmware compatibility; confirm battery health; full‑system commissioning test mandatory before unit put‑into‑service.

Reviews

There are no reviews yet.

Be the first to review “GE IC693CPU374 Series 90‑30 High‑Performance Built‑in Dual‑Port Ethernet CPU Module”