Hardware & Electrical Specifications
‑ Model:IC693CPU374 ‑ Part Number:IC693CPU374 ‑ Module Type:Series‑90‑30 High‑Performance Dual‑Port On‑Board Ethernet CPU Module ‑ Mounting:Dedicated CPU slot on Series‑90‑30 main baseplate ‑ Processor:Embedded 586, 133 MHz ‑ Backplane power:5 VDC @1480 mA, power consumption 7.4W, high‑capacity power supply recommended ‑ Logic execution speed:0.15 ms / 1K Boolean logic instruction ‑ User program memory:240 KB configurable Flash/RAM, program can be stored in flash memory ‑ I/O capacity: • Discrete input %I:2048 points • Discrete output %Q:2048 points • Analog input %AI:max 32640 words • Analog output %AQ:max 32640 words • Register %R:128‑32640 configurable words • Timers/Counters:>2000 sets (depends on memory) ‑ Rack expansion:Max 8 racks total (1 CPU base +7 expansion racks) ‑ Communication interfaces: • Dual RJ45 10/100Mbps Ethernet with built‑in switch, support daisy‑chain network wiring • No onboard serial port; SNP‑X RS‑485 port located on power‑supply module ‑ Supported Ethernet protocols:SRTP server/client, EGD Ethernet Global Data, Modbus‑TCP master/slave ‑ Memory backup:RTC clock & RAM data backed up by power‑supply internal battery; external battery IC693ACC302 extends backup time to 15 months ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:Hardware watchdog timer, comprehensive system self‑diagnosis, power‑fail detection ‑ Compatibility note:Cannot run standalone; must install in dedicated CPU slot of Series‑90‑30 baseplate; high‑capacity power supply is recommended; full system download & I/O verification test mandatory after replacement。
Environmental Specifications
‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight:approx 0.40 kg ‑ Dimension:Series‑90‑30 standard single‑slot CPU module form‑factor ‑ Handling note:ESD‑sensitive high‑speed logic circuit, anti‑static wrist‑strap mandatory during handling; pay attention to backup‑battery status during maintenance
Main Functions
- Execute ladder logic, function block, structured‑text user program; hardware floating‑point arithmetic, periodic interrupt subroutine processing.
- Dual‑port integrated Ethernet switch, realize PLC programming download, HMI connection, EGD inter‑PLC data exchange, Modbus‑TCP third‑party device communication, support network daisy‑chain wiring, save network switch hardware.
- Manage backplane bus, realize data exchange with local I/O, special‑function modules and multi‑expansion racks.
- System‑level fault diagnosis: power failure, program error, I/O fault, watchdog overtime; store fault log; support EZ‑Store offline program download without PC.
- LED status indication on front panel: ‑ Green RUN:CPU run mode indicator ‑ Red FAULT:CPU hardware / program fault alarm ‑ Green OK:Power‑on and self‑test pass indicator ‑ LAN1 / LAN2:Ethernet link / activity indicator
Installation & Wiring Requirements
- Cut off full PLC rack power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling CPU module.
- Insert IC693CPU374 into dedicated CPU slot on main baseplate and lock latch; check power‑supply backup‑battery condition.
- If using expansion racks, connect official GE expansion cable between main‑base and expansion‑base 25‑pin D‑sub port.
- Use industrial shielded Ethernet cable for network wiring; separate network cables from high‑power cables; complete protective grounding according to GE Series‑90‑30 hardware manual specification.
- After replacement:power‑on PLC, verify RUN / OK / FAULT / LAN LED status; set IP address, download hardware configuration & user program; perform full local & expansion‑rack I/O test and Ethernet communication test.
- Replacement note: Verify project firmware compatibility; confirm battery health; full‑system commissioning test mandatory before unit put‑into‑service.