GE IC693CPU374 Series 90‑30 High‑Performance CPU Module, Dual‑Port 10/100Mbps Embedded Ethernet

Top‑tier single‑slot CPU for Series 90‑30 PLC platform.
133 MHz high‑speed processor, 240 KB configurable user memory, dual‑port 10/100 Mbps Ethernet with built‑in switch.
Max 2048 discrete I/O points, optimized for medium‑to‑large‑scale industrial automation systems.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware Specifications

  • Processor: AMD SC520, 133 MHz, floating‑point calculation supported
  • User Memory: 240 KB configurable RAM/Flash memory
  • I/O Capacity: Max 2048 discrete inputs / 2048 discrete outputs; register memory up to 32640 words
  • Scan Speed: ~0.15 ms per 1K boolean logic contacts
  • Communication: Dual 10/100Mbps auto‑sensing Ethernet ports (built‑in switch); Station Manager RJ‑11 maintenance port; SNP/SNPX serial via power‑supply port; supports SRTP, EGD, Modbus TCP Client/Server
  • Power: 5 VDC, 7.4 W, single‑slot backplane installation
  • Operating Temperature: 0 °C ~ 60 °C; storage‑40 °C ~ 85 °C
  • Expansion: 1 main baseplate + up to 7 expansion / remote I/O baseplates (total 8 racks)
  • Programming Software: Proficy Machine Edition, VersaPro

Core Functions

  • Execute ladder‑logic, function‑block programs with watchdog safety supervision.
  • Support PID loop control, high‑speed counter, interrupt subroutine and floating‑point arithmetic.
  • Dual‑port Ethernet enables daisy‑chain networking, HMI connection, peer‑to‑peer PLC data exchange.
  • Built‑in station‑manager console for IP address setup and basic diagnostics.
  • Comprehensive system diagnostics, fault logging; battery‑backed RAM preserves program and real‑time clock during power loss.

Installation Requirements

  • Mount into dedicated CPU slot of Series 90‑30 main baseplate.
  • Confirm rack power‑supply provides sufficient 5 VDC current for CPU and other modules.
  • Install IC693ACC302 lithium backup‑battery module for memory retention at power‑off.
  • Operate within 0‑60℃ ambient, avoid heavy dust, vibration and condensation.
  • Complete hardware configuration before downloading user application program.
  • Configure Ethernet IP via Proficy Machine Edition or RJ‑11 station‑manager port.

Common Fault Modes

  1. CPU fault LED illuminated: watchdog timeout, program error, memory parity fault, configuration mismatch.
  2. Unable to enter RUN mode: program missing, hardware config mismatch, key‑switch set to STOP.
  3. Ethernet communication failure: cable defect, incorrect IP/subnet setting, protocol parameter mismatch.
  4. Program & register data lost after power‑cycle: backup‑battery low voltage or defective.
  5. Real‑time clock failure: backup‑battery exhausted, battery replacement required.
  6. Cannot access station‑manager console: wrong cable type, incorrect serial communication parameters.

Reviews

There are no reviews yet.

Be the first to review “GE IC693CPU374 Series 90‑30 High‑Performance CPU Module, Dual‑Port 10/100Mbps Embedded Ethernet”

Your email address will not be published. Required fields are marked *