Description
Hardware Specifications
- Compatibility: GE Series 90‑30 PLC backplane, single‑slot installation
- Network: DeviceNet master mode, baud‑rate 125 k / 250 k / 500 k bps
- Max Slave Nodes: 63 DeviceNet slave devices
- Service Port: RS‑232 for module setup, diagnostics and firmware update
- Power Requirement: 5 VDC from PLC backplane
- Operating Temperature: 0 °C ~ 60 °C
- Storage Temperature: ‑40 °C ~ 85 °C
- Programming Software: Proficy Machine Edition, DeviceNet configuration tool
- Note: IC693DNM is incomplete part number; full valid part number is IC693DNM200
Core Functions
- Operates as DeviceNet master station, handles I/O data polling and explicit message communication.
- Multiple connection modes: polled, change‑of‑state, strobe for slave‑device data exchange.
- Transmits and receives large‑size input/output data for DeviceNet slaves.
- Built‑in module diagnostics, network fault detection and status LED indication.
- RS‑232 port for local configuration without relying on PLC CPU download path.
Installation Requirements
- Insert IC693DNM200 into any available slot on Series 90‑30 main or expansion baseplate.
- Terminate DeviceNet bus with proper 121Ω bus terminators at both physical ends.
- Verify DeviceNet bus power supply meets field‑bus specification.
- Set correct baud‑rate matching all slave‑devices on the DeviceNet network.
- Operate within 0‑60℃ ambient; avoid heavy dust, vibration and condensation.
- Complete network configuration before putting the system into RUN status.
Common Fault Modes
- Module status LED alarm: bus short‑circuit, missing bus termination, baud‑rate mismatch.
- Slave‑device offline: wrong node address, bus‑power insufficient, cable damage.
- I/O data loss: incorrect connection configuration, slave‑device fault.
- Cannot configure module via RS‑232: wrong cable type, incorrect serial‑port parameters.
- Intermittent communication: poor bus‑grounding, signal reflection without terminators.