Description
Hardware & Electrical Specifications
‑ Model:IC693PWR322 ‑ Part Number:IC693PWR322 ‑ Module Type:Series‑90‑30 30W DC‑Input Rack Power‑Supply Module ‑ Mounting:Far‑left dedicated power‑supply slot on Series‑90‑30 main baseplate only ‑ Input range:18‑56 VDC, nominal 24/48 VDC, minimum startup voltage 21VDC ‑ Max input power:50W ‑ Peak inrush current:4A / 100 ms max ‑ Output rails (total 30W combined maximum): • +5 VDC backplane logic:15 W, supplies CPU & all back‑plane modules • +24 VDC Relay power:15 W, drives relay‑type output modules • Isolated +24 VDC auxiliary:20 W, isolated auxiliary power supply ‑ Serial port:RS‑485 SNP‑X port on front terminal, for programming, HMI, SNP‑X slave communication ‑ Built‑in protection:Over‑voltage, over‑current, short‑circuit protection ‑ Memory backup:External lithium battery required for RTC clock & CPU RAM data retention, battery not supplied with module ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ Compatibility note:Cannot install in I/O slot or expansion racks; calculate total 5VDC consumption of all main‑rack modules, must not exceed power budget; expansion racks must use separate power supply; full rack power‑load check mandatory after replacement。
Environmental Specifications
‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight:approx 0.35 kg ‑ Dimension:Series‑90‑30 standard single‑slot power‑supply form‑factor ‑ Handling note:ESD‑sensitive power circuit; battery needs to be purchased separately; check battery aging during maintenance ‑ Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Main‑rack power source, converts field 24/48VDC input into +5VDC logic bus, +24V relay‑drive and isolated 24V auxiliary power for main‑base CPU and I/O modules.
- Integrated RS‑485 SNP‑X serial port, serves as program download and HMI communication channel for CPUs without onboard serial port.
- Supports external backup‑battery to preserve real‑time clock and CPU RAM data during power‑off.
- Hardware protective function for over‑voltage, over‑current and short‑circuit fault.
- LED status indication on front panel: ‑ Green OK:Power‑supply normal output indicator ‑ FAULT:Over‑voltage / over‑current / short‑circuit alarm ‑ BATT:Low‑battery warning indicator
Installation & Wiring Requirements
- Cut off PLC main DC input power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling power‑supply module.
- Insert IC693PWR322 into far‑left dedicated power‑supply slot of main baseplate and lock latch; install external backup‑battery if needed.
- DC main‑source power wiring strictly follow GE hardware manual; use suitable‑rating wire and external circuit breaker; separate power input cable from signal cables, connect protective ground reliably.
- RS‑485 SNP‑X serial wiring: use shielded twisted‑pair, install terminating resistor at bus tail end.
- After replacement:power‑on main DC input, verify OK / FAULT / BATT LED status; measure three DC output rail voltage; verify SNP‑X serial communication; calculate total 5VDC load consumption of all plug‑in modules.
- Replacement note: Confirm main‑rack total power consumption within 30W rating; expansion racks cannot draw power from this power‑supply; pay attention to battery health; full‑system power‑on commissioning test mandatory before unit put‑into‑service。



-1-1-300x300.jpg)


Reviews