GE IC693PWR331C Series 90‑30 High‑Capacity 30W DC‑Input Rack Power Supply Module

IC693PWR331C is high‑capacity DC‑input power supply for GE Fanuc Series‑90‑30 PLC platform, C denotes hardware revision. It must be mounted at the far‑left dedicated power‑supply slot of main baseplate, cannot be installed in ordinary I/O slot or expansion racks. Nominal input 24 VDC, wide operating DC input range. The biggest advantage compared with PWR322: the full 30‑W total power can be allocated entirely to +5 VDC backplane bus, suitable for main‑rack loaded with many high‑power consumption modules (CPU374, communication modules, special‑function modules). Provides three regulated DC outputs: +5VDC logic bus, +24VDC relay drive power, isolated auxiliary +24VDC. Equipped with front‑panel RS‑485 SNP‑X serial port, used for programming download and HMI connection for CPUs without built‑in serial port. Require external lithium battery for RTC clock and RAM data backup, battery not delivered together with module. Over‑voltage, over‑current, short‑circuit built‑in protection. Expansion racks still need independent local power supply. Product status: Obsolete, spare‑part only supply available。

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware & Electrical Specifications

‑ Model:IC693PWR331C ‑ Part Number:IC693PWR331C ‑ Module Type:Series‑90‑30 High‑Capacity 30W DC‑Input Power‑Supply Module ‑ Mounting:Far‑left dedicated power‑supply slot on Series‑90‑30 main baseplate only ‑ Input:  • Nominal:24 VDC  • Operating range:2‑30 VDC; Minimum startup voltage:8 VDC ‑ Max input power:50 W ‑ Total rated output power:30 W, flexible power distribution, can assign all 30W to +5 VDC rail ‑ Output rails:  • +5 VDC backplane logic bus:max 30W (flexible allocation)  • +24 VDC Relay drive power:for relay‑output modules  • Isolated +24 VDC auxiliary power:isolated auxiliary supply ‑ Serial interface:Front‑terminal RS‑485 SNP‑X port, SNP‑X slave, for programming, HMI communication ‑ Protection:Over‑voltage, over‑current, short‑circuit, foldback current‑limiting for +5 V rail ‑ Memory backup:External lithium battery IC693ACC301 required for RTC & RAM data retention, battery not included ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ Compatibility note:Cannot install in I/O‑slot or expansion racks; calculate total 5VDC power consumption of all modules in main rack; expansion racks must use separate power‑supply; full‑load power budget check mandatory after replacementQualitrol。

Environmental Specifications

‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification

Mechanical Data

‑ Weight:approx 0.36 kg ‑ Dimension:Series‑90‑30 standard single‑slot power‑supply form‑factor ‑ Handling note:ESD‑sensitive power circuit; battery must be purchased separately; check battery aging status during maintenance ‑ Terminal tightening torque:0.6‑1.0 N·m

Main Functions

  1. Main‑rack high‑capacity DC power source, convert field 24 VDC input into +5 VDC logic bus, +24 V relay‑drive and isolated auxiliary 24 V power for CPU and all back‑plane modules; support full 30W power assigned to +5 V bus for heavy‑load main‑rack.
  2. Integrated RS‑485 SNP‑X serial port, serves as program download and HMI communication channel for CPUs without onboard serial port.
  3. Cooperate with external backup‑battery, preserve real‑time clock and CPU RAM data upon power‑off.
  4. Built‑in hardware protection for over‑voltage, over‑current and short‑circuit fault.
  5. LED status indication on front panel:   ‑ Green OK:Power‑supply normal output indicator   ‑ FAULT:Over‑voltage / over‑current / short‑circuit fault alarm   ‑ BATT:Low‑battery warning indicator

Installation & Wiring Requirements

  1. Cut off PLC main DC‑input power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling power‑supply module.
  2. Insert IC693PWR331C into far‑left dedicated power‑supply slot of main baseplate and lock latch; install external backup‑battery if needed.
  3. DC‑input power wiring strictly follow GE hardware manual; match proper‑rating wire and external circuit‑breaker; separate power input cable from signal cables, reliable protective‑ground connection.
  4. RS‑485 SNP‑X wiring: use shielded twisted‑pair, install terminating resistor at bus tail‑end.
  5. After replacement:power‑on main DC‑input, verify OK / FAULT / BATT LED status; measure each DC output rail voltage; verify SNP‑X serial communication; calculate total 5VDC load consumption of all plug‑in modules.
  6. Replacement note: Confirm main‑rack total power consumption within 30W rating; expansion racks cannot draw power from this power‑supply; inspect battery health; full‑system commissioning test mandatory before unit put‑into‑service。