Description
Hardware & Electrical Specifications
‑ Model:IC694ALG222 ‑ Part Number:IC694ALG222 ‑ Module Type:RX3i / 90‑30 Analog Voltage Input Module ‑ Mounting:Plug‑in any slot of RX3i universal backplane / Series‑90‑30 base or expansion rack ‑ Backplane power:5 VDC @112 mA drawn from rack backplane ‑ External isolated power:24 VDC, typical 110 mA (new‑revision hardware) ‑ Channel configuration: • Single‑ended:16 channels, voltage input • Differential:8 channels, voltage input ‑ Input signal range (per‑channel configurable):0‑10 V DC, ‑10 ~ +10 V DC ‑ A/D resolution:12‑bit ‑ Conversion update rate: • 16‑channel single‑ended:6 ms full‑scan • 8‑channel differential:3 ms full‑scan ‑ Input impedance:>1 MΩ ‑ Diagnostics:Over‑range, under‑range detection; module hardware self‑diagnosis ‑ Isolation:Field‑to‑logic backplane 250 VAC continuous withstand; no channel‑to‑channel isolation ‑ Termination:Requires separate 36‑pin terminal block IC694TBB032 / IC694TBS032 ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ Compatibility note:Cannot run standalone; external isolated 24VDC must be supplied; differential mode improves anti‑interference for long‑signal‑wire; full analog‑loop simulation test mandatory after replacement。
Environmental Specifications
‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight:approx 0.28 kg ‑ Dimension:RX3i single‑slot module form‑factor ‑ Handling note:ESD‑sensitive analog measuring circuit; analog signal must use shielded twisted‑pair cable; strictly distinguish single‑ended / differential wiring
Main Functions
- Collect field voltage analog signals from pressure, displacement, potentiometer‑type sensors, convert analog voltage into digital value for PLC CPU processing.
- Two wiring modes optional: single‑ended for multi‑point short‑distance acquisition; differential mode for long‑distance site with strong electromagnetic interference.
- Channel‑level diagnosis: judge signal over‑range / under‑range fault, upload alarm status to PLC register.
- Real‑time data exchange with CPU via backplane bus, transmit converted analog register values.
- LED status indication on front panel: ‑ Green P/S OK:Module internal 5V power supply normal ‑ Green MODULE OK:Module hardware & configuration normal; flashing indicates configuration error / fault
Installation & Wiring Requirements
- Cut off PLC rack power and external isolated 24VDC power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling module.
- Insert IC694ALG222 fully into backplane slot and lock latch; install matched terminal block IC694TBB032 / IC694TBS032.
- Analog signal wiring must adopt shielded twisted‑pair; separate analog signal cable from high‑power power cable; cable shield single‑end grounding; strictly follow single‑ended / differential wiring definition of manual.
- External isolated 24VDC power supply wiring comply with GE hardware manual, add external fuse protection.
- After replacement:power‑on rack and isolated 24VDC; verify P/S OK and MODULE OK LED status; download hardware configuration; perform full‑channel signal input simulation test.
- Replacement note: Pay attention to new‑revision higher 24VDC current consumption; correctly select single‑ended / differential mode according to field site; full‑system commissioning test mandatory before unit put‑into‑service。




-1-1-300x300.jpg)

Reviews