Description
Hardware & Electrical Specifications
‑ Model:IC694MDL655 ‑ Part Number:IC694MDL655 ‑ Module Type:RX3i 32‑Channel 24VDC Discrete Input Module ‑ Mounting:Plug‑in any slot on RX3i universal backplane, local main rack or expansion rack ‑ Backplane power:5 VDC @140 mA drawn from rack backplane ‑ Field input: • Rated voltage:24 VDC, operating range 10‑30 VDC • Input current:7 mA typical @24VDC per channel • Logic selection:Each group hardware jumper select POS(positive/sourcing) / NEG(negative/sinking) • ON threshold:≥10 VDC • OFF threshold:≤5 VDC • Response time:ON/OFF max 2 ms ‑ Isolation:Field‑to‑backplane 1500 VAC 1‑minute withstand; group‑to‑group isolation; no isolation between channels within same group ‑ Termination:Requires separate 36‑pin terminal block IC694TBB032 / IC694TBS032 ‑ Diagnostics:Module self‑diagnosis; channel input status feedback to CPU register ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ Compatibility note:Cannot run standalone; field 24VDC power must be externally supplied; jumper setting must match field sensor type; full discrete‑input loop simulation test mandatory after replacement。
Environmental Specifications
‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight:approx 0.24 kg ‑ Dimension:RX3i single‑slot module form‑factor ‑ Handling note:ESD‑sensitive input circuit; pay attention to group jumper setting before power‑on; separate signal cables from high‑power cables
Main Functions
- Collect field discrete signals: proximity switches, limit switches, push‑buttons, relay auxiliary contacts; convert field 24VDC on/off signal into digital data for RX3i CPU.
- Four independent groups, each group can switch sourcing / sinking logic by hardware jumper, adapt to different sensor wiring schemes.
- Real‑time data exchange with CPU via backplane bus, upload 32‑point input status to PLC discrete‑input register.
- LED status indication on front panel: ‑ Green P/S OK:Module 5V backplane power normal ‑ Green MODULE OK:Module hardware & configuration normal ‑ 32 individual green channel LED:Real‑time status indicator for each input channel
Installation & Wiring Requirements
- Cut off PLC rack power and field 24VDC input power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling module.
- Insert IC694MDL655 fully into backplane slot and lock latch; install matched terminal block; set group POS/NEG jumpers according to field sensor type.
- Field signal wiring strictly follow GE RX3i hardware manual; use shielded twisted‑pair for long‑distance signal; separate input signal cables from high‑power cables; reliable protective‑ground connection.
- After replacement:power‑on rack and field 24VDC; verify P/S OK、MODULE OK and channel LED status; download hardware configuration; perform full‑channel input trigger test.
- Replacement note: Double‑check jumper logic matches field device; avoid wrong jumper causing signal abnormal; full‑system commissioning test mandatory before unit put‑into‑service。