Description
Hardware & Electrical Specifications
‑ Model:IC694MDL753 ‑ Part Number:IC694MDL753 ‑ Module Type:RX3i 32‑Point 12/24VDC Sourcing (Positive Logic) Output Module ‑ Mounting:Plug‑in any slot on RX3i universal backplane, main rack or expansion rack ‑ Backplane power:5 VDC @260 mA drawn from rack backplane ‑ Field load power:External 10.2‑28.8 VDC (nominal 12‑24VDC) supplied by user power supply ‑ Output capacity: • Per‑channel max resistive current:0.5 A • Per‑group maximum total current:4 A • Output type:Sourcing / positive logic, module outputs positive voltage to load ‑ Response time:Turn‑ON / Turn‑OFF ≤1ms typical ‑ Isolation: • Field‑to‑logic backplane:Optocoupler isolation, 1500 VAC 1‑minute withstand • Group‑to‑group isolation:500 VAC; no isolation between channels inside same group ‑ Terminal:Requires separate 36‑pin terminal block IC694TBB032 / IC694TBS032 ‑ Diagnostics:Module self‑diagnosis; no built‑in per‑channel short‑circuit detection; all outputs forced OFF at CPU STOP mode ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ Compatibility note:Cannot run standalone; external field DC power must be provided; inductive loads need free‑wheel diode absorption; full discrete‑output loop simulation test mandatory after replacement。
Environmental Specifications
‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight:approx 0.25 kg ‑ Dimension:RX3i single‑slot module form‑factor ‑ Handling note:ESD‑sensitive output drive circuit; inductive loads must add absorption components; pay attention to per‑group 4A total‑current limit; use both common pins for high‑current group connection
Main Functions
- 32‑point sourcing DC output, drive field solenoid valves, DC contactor coils, indicator lamps and other 12/24VDC field actuators.
- Four independent groups, each group can adopt different supply voltage, flexible for mixed‑voltage field equipment.
- Receives output data from RX3i CPU via backplane bus, controls ON/OFF status of each channel. When CPU enters STOP state, all outputs turn off for safety.
- LED status indication on front panel: ‑ Green P/S OK:Module 5V backplane power supply normal ‑ Green MODULE OK:Module hardware & configuration normal ‑ 32 individual green channel LED:Real‑time status indicator for each output channel
Installation & Wiring Requirements
- Cut off PLC rack power and external field 12/24VDC load power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling module.
- Insert IC694MDL753 fully into backplane slot and lock latch; install matched terminal block.
- Field wiring strictly follow GE RX3i hardware manual; for inductive coil loads, parallel free‑wheel diode absorption circuit; add external fuse for each output group; separate output signal cables from high‑power cables, reliable protective‑ground connection.
- After replacement:power‑on rack and field DC power; verify P/S OK、MODULE OK and channel LED status; download hardware configuration; perform full‑channel output trigger test.
- Replacement note: Strictly control each group total current ≤4A; high‑current group must connect both common pins on terminal block; no channel short‑circuit alarm on module side, external fuse protection is essential; full‑system commissioning test mandatory before unit put‑into‑service。