Description
Hardware & Electrical Specifications
‑ Model:IC694MDL940 ‑ Part Number:IC694MDL940 ‑ Module Type:RX3i 16‑Point 2A Relay Output Module ‑ Mounting:Plug‑in any I/O slot of RX3i backplane, main rack or expansion rack ‑ Backplane power consumption: • 5VDC bus:7 mA (all outputs ON) • 24VDC relay‑drive bus:135 mA (all outputs ON) ‑ Output channel:16‑point NO normally‑open relay output, 4 groups ×4 points ‑ Load voltage range: • DC:5‑30 VDC • AC:5‑250 VAC, 47‑63Hz ‑ Load current: • Per‑channel resistive max:2 A • Per‑group common terminal max:4 A • Minimum load current:10 mA • Peak inrush current:5 A max ‑ Response time:ON max 15 ms; OFF max 15 ms ‑ Isolation: • Field‑to‑logic backplane:1500 VAC 1‑minute withstand • Group‑to‑group isolation:500 VAC • No isolation between points inside same group ‑ Terminal:20‑pin captive screw terminal block ‑ Diagnostics:Module self‑diagnosis; no per‑channel short‑circuit detection ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ Compatibility note:Cannot run standalone; inductive loads must install free‑wheel diode / RC‑snubber absorption circuit; external fuse required for each group; full discrete‑loop simulation test mandatory after replacement。
Environmental Specifications
‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor industrial control cabinet, IP20 ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight:approx 0.36 kg ‑ Dimension:RX3i single‑slot module form‑factor ‑ Handling note:ESD‑sensitive relay‑drive circuit; inductive loads need absorption components; strictly control per‑group 4A current limit
Main Functions
- Drive field‑side solenoid valves, contactors, indicator lamps, motor‑starter auxiliary coils, support AC and DC mixed‑load switching.
- Receive output data from RX3i CPU over backplane bus, actuate internal relay contacts to switch external field power circuit.
- LED status indication on front panel: ‑ Green PWR:Module internal power‑on indicator ‑ 16 individual channel green LEDs:Real‑time ON/OFF status for each output
Installation & Wiring Requirements
- Cut off PLC rack power and external field‑load power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling module.
- Insert IC694MDL940 fully into RX3i backplane I/O slot and lock latch.
- Field wiring strictly follow GE RX3i hardware manual; inductive coil loads must add RC‑snubber or free‑wheel‑diode; install external fuse for every output group; separate signal cables from high‑power cables, reliable protective‑ground connection.
- After replacement:power‑on rack and field‑load power; verify PWR and channel LED status; perform full‑channel output trigger test.
- Replacement note: Per‑group total current shall not exceed 4A; no built‑in channel fuse; absorption protection is essential for inductive loads; full‑system commissioning test mandatory before unit put‑into‑service。