Description
Hardware & Electrical Specifications
‑ Model: IC695CPU320 ‑ Part Number: IC695CPU320 ‑ Module Type: RX3i High‑Performance CPU Controller, occupies 2 consecutive slots on universal backplane ‑ Mounting: Main‑rack universal backplane IC695CHS series only; cannot be installed on expansion backplane ‑ Backplane power consumption: • +3.3 VDC: 1000 mA nominal • +5 VDC: 1200 mA nominal ‑ Processor: 1 GHz Intel Celeron‑M ‑ User memory: 64 MB battery‑backed SRAM + 64 MB non‑volatile Flash memory ‑ Logic execution speed: 0.047 ms / 1000 Boolean instructions typical ‑ I/O capacity: • Discrete %I / %Q: 32 K bits • Analog %AI / %AQ: 32 K words each ‑ Program blocks: Max 512 blocks; each block maximum size 128 KB ‑ On‑board communication interfaces: • COM1: RS‑232 (9‑pin D‑sub), SNP‑Slave, Modbus‑RTU Slave • COM2: RS‑485 half‑duplex (15‑pin D‑sub), Modbus‑RTU Master/Slave, SNP‑Slave ‑ Ethernet: No onboard port; requires separate IC695ETM001 Ethernet module ‑ RTC real‑time clock: Max drift 2 seconds per day, lithium battery backup, typical service life 5 years ‑ Expansion capacity: Maximum 8 local expansion racks ‑ Required battery accessory: IC695ACC302 smart lithium battery module ‑ Diagnostics: CPU hardware self‑test, backplane bus fault, I/O fault monitoring, memory checksum and ECC error detection ‑ PCB treatment: Conformal coated for dust, moisture and corrosion resistance ‑ Compatibility note: CPU hot‑swap is forbidden. Verify total backplane power budget before installation. Legacy Series‑90‑30 modules are supported with restrictions, refer to system manual GFK‑2314. Full system download and I/O validation test must be performed after replacement.
Environmental Specifications
‑ Operating temperature: 0 ℃ ~ +60 ℃ ‑ Storage temperature: ‑40 ℃ ~ +85 ℃ ‑ Relative humidity: 5%‑95% non‑condensing ‑ Installation location: Indoor control cabinet, IP20 protection class ‑ EMC compliance: IEC 61000‑6‑2 ‑ Certifications: CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight: approx 1.05 kg (2.31 lbs) ‑ Dimension: RX3i dual‑slot CPU module form‑factor ‑ Handling note: ESD‑sensitive high‑speed processor circuitry. Periodically inspect smart lithium battery aging status. No onboard USB port.
Main Functions
- High‑performance main processing unit for RX3i automation system. Executes IEC 61131‑3 user logic, floating‑point arithmetic, handles local and expansion‑rack I/O via dual PCI / serial backplane bus.
- Two onboard serial ports for Modbus‑RTU field instruments and SNP communication. Ethernet functions are realized by external ETM001 module for SCADA, Modbus‑TCP and EGD data exchange.
- Program and configuration stored in non‑volatile flash; runtime process data maintained by battery‑backed SRAM. Supports in‑system firmware upgrade for CPU and other backplane modules.
- Front‑panel LED indicators: ‑ Green CPU OK: CPU hardware normal status ‑ Red SYS FLT: Hardware / memory / configuration system fault ‑ Green RUN: User program executing ‑ OUTPUTS ENABLED: Output scan active ‑ I/O FORCE: I/O force function active ‑ BATTERY: Low battery alarm ‑ COM1 / COM2: Serial communication activity status
Installation & Wiring Requirements
- Cut off full rack power supply before replacement. CPU hot‑swap is strictly forbidden. ESD protection must be applied during module handling.
- Insert IC695CPU320 into two consecutive slots of RX3i universal main‑rack backplane and engage locking latches. Install IC695ACC302 smart battery module.
- Serial wiring comply with GE RX3i hardware manual. Use shielded twisted‑pair for RS‑485 bus; install terminating resistor at bus end. Reliable protective‑ground connection is required. If Ethernet is needed, install IC695ETM001 module on backplane.
- After replacement: Power‑on rack power, check CPU front‑panel LED status. Download hardware configuration and user application program. Complete I/O mapping validation and all communication link tests.
- Replacement note: Confirm backplane provides sufficient 3.3 V / 5 V current capacity. Inspect battery health status. Full‑system commissioning test is mandatory before putting into service.





-1-1-300x300.jpg)


Reviews
There are no reviews yet.