GE IC695RMX128 PACSystems RX3i Redundancy Memory Xchange Module

IC695RMX128 is a single‑slot hot‑swappable Redundancy Memory Xchange (RMX) module for GE PACSystems RX3i platform. It provides high‑speed fiber‑optic reflective‑memory link for IC695CRU320 hot‑standby redundant CPU systems, performing real‑time runtime data synchronization between primary and standby CPUs to achieve bumpless switchover upon active‑CPU failure. It can also operate as a general‑purpose reflective‑memory peer‑to‑peer communication module (functionally equivalent to IC695CMX128) for multi‑controller deterministic data sharing over fiber ring networkfiles.kemp….

It contains 128 MB shared reflective memory, two SFP transceiver slots for fiber connection (SFP modules purchased separately). Data transfer rate reaches 2.12 Gbaud, sub‑microsecond per‑node latency, supports up to 256 nodes on one reflective‑memory ring network. When used for hot‑standby redundancy, point‑to‑point fiber connection between two RMX128 modules is adopted, maximum multimode fiber distance 300 metersfiles.kemp…. No hardware jumpers; all node and network parameters are configured via Proficy Machine Edition software. Reference manual GFK‑2511C. Product status: Obsolete, spare‑part supply only.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware & Electrical Specifications

‑ Model: IC695RMX128 ‑ Part Number: IC695RMX128 ‑ Module Type: RX3i Redundancy Memory Xchange Module, occupies 1 single slot on universal backplane ‑ Mounting: Main‑rack universal backplane IC695CHS series only; cannot be installed on expansion backplanesfiles.kemp… ‑ Backplane power consumption:  • +3.3 VDC: 580 mA nominal  • +5 VDC: 220 mA nominal ‑ Shared reflective memory: 128 MB ‑ Fiber interfaces: 2 × SFP slots (LC connector), SFP transceivers not included ‑ Data transfer rate: 2.12 Gbaud ‑ Network topology: Point‑to‑point for CPU redundancy; daisy‑chain ring for multi‑node reflective‑memory network ‑ Maximum nodes per ring: 256 nodes ‑ Max multimode fiber distance: 300 m ‑ Redundancy system requirement: One RMX128 module for each CRU320 CPU in hot‑standby pair ‑ Hot‑swap: Supported (RIUP Remove and Insert Under Power) ‑ Diagnostics: Module self‑test, fiber link status, sync error counter, reflective‑memory network fault, redundancy synchronization status reporting to host CPU ‑ PCB treatment: Conformal coated for dust, moisture and corrosion resistance ‑ Compatibility note: Drop‑in compatible with IC695RMX228. Supports IC695CRU320 redundancy CPU, also works with CPU315 / CPU320 / CPE‑series CPUs as CMX‑mode peer‑communication module. RX3i main rack supports maximum six Memory Xchange modules combined (RMX128 + CMX128), maximum two RMX modules for redundancy link. Verify total backplane power budget before installation. After replacement, download hardware configuration and perform redundancy synchronization and bumpless switchover validation test.

Environmental Specifications

‑ Operating temperature: 0 ℃ ~ +60 ℃ ‑ Storage temperature: ‑40 ℃ ~ +85 ℃ ‑ Relative humidity: 5%‑95% non‑condensing ‑ Installation location: Indoor control cabinet, IP20 protection class ‑ EMC compliance: IEC 61000‑6‑2 ‑ Certifications: CE, UL Class I Div 2 hazardous‑location certification

Mechanical Data

‑ Weight: approx 0.42 kg ‑ Dimension: RX3i single‑slot module form‑factor ‑ Handling note: ESD‑sensitive high‑speed fiber communication circuitry. Use GE‑qualified SFP transceivers. Observe correct TX‑RX cross‑connection for fiber cabling.

Main Functions

  1. Dedicated high‑speed synchronization link for RX3i hot‑standby redundant system. Real‑time mirrors primary CPU runtime data to standby CPU via reflective‑memory fiber channel, ensures bumpless automatic switchover when active CPU fails.
  2. When configured in CMX mode, implements deterministic peer‑to‑peer data exchange among multiple PACSystems controllers on reflective‑memory ring network, no CPU scan‑cycle overhead for memory replication.
  3. Front‑panel LED indicators:   ‑ Green MOD OK: Module hardware normal status   ‑ Red NET FLT: Fiber link / network synchronization fault   ‑ ACTIVE: Reflective‑memory network operational   ‑ LINK1 / LINK2: Fiber port link and activity status

Installation & Wiring Requirements

  1. Cut off full rack power supply for initial installation; hot‑swap replacement is permitted. Apply ESD protection during module handling.
  2. Insert IC695RMX128 into single slot of RX3i universal main‑rack backplane and engage locking latch. Install compatible SFP fiber transceivers. Cross‑connect TX‑RX fiber cables between paired RMX modules for redundancy application.
  3. Fiber wiring comply with GE RX3i manual GFK‑2511C. Observe transmit‑receive polarity. Reliable protective‑ground connection is required. Configure redundancy transfer‑list in Proficy Machine Edition for hot‑standby system.
  4. After replacement: Power‑on rack power, check front‑panel LED status. Download hardware configuration and application project. Verify fiber link health, redundancy synchronization status and manual bumpless switchover performance.
  5. Replacement note: Confirm host CPU firmware meets minimum revision requirement. Check fiber cable attenuation and polarity. Full‑system commissioning test is mandatory before putting into service.