Description
Hardware & Electrical Specifications
‑ Model: IC697BEM721 ‑ Part Number: IC697BEM721 ‑ Module Type: Series 90‑70 Main‑Rack Bus Expansion Module, occupies one slot on Series 90‑70 backplane ‑ Mounting: Standard Series 90‑70 main rack only; cannot be used in remote expansion racks ‑ Backplane power consumption: • +5 VDC: 650 mA maximum ‑ Expansion bus interface: D‑Sub 50‑pin female connector for remote‑rack parallel bus cable ‑ Max supported remote racks: 7 remote racks per BEM721 ‑ Max cable length: 200 m between BEM721 and first BEM731 remote module ‑ Bus topology: Daisy‑chain connection for multiple remote racks ‑ Matching remote‑rack partner module: IC697BEM731 ‑ Diagnostics: Module self‑test, cable link fault, remote rack dropout detection, parity error checking, fault alarm reported to Series‑90‑70 CPU ‑ PCB treatment: Conformal coated for dust, moisture and corrosion resistance ‑ Compatibility note: Only for Series 90‑70 platform; incompatible with RX3i / VersaMax hardware. Must pair with IC697BEM731 in every remote rack. Hot‑swap is prohibited. After replacement, download hardware configuration and perform remote‑rack online validation test.
Environmental Specifications
‑ Operating temperature: 0 ℃ ~ +60 ℃ ‑ Storage temperature: −40 ℃ ~ +85 ℃ ‑ Relative humidity: 5%‑95% non‑condensing ‑ Installation location: Indoor control cabinet, IP20 protection class ‑ EMC compliance: IEC 61000‑6‑2 ‑ Certifications: CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight: approx 0.70 kg ‑ Dimension: Series 90‑70 standard single‑slot module form‑factor
Main Functions
- Acts as main‑rack master for Series 90‑70 remote expansion bus, communicates with IC697BEM731 modules located in remote racks, extends PLC I/O points without adding slots in main CPU rack.
- Parallel high‑speed bus ensures fast refresh of digital and analog I/O located in distributed remote racks.
- Comprehensive link diagnostics to detect broken cable, remote rack power‑loss and communication parity errors.
- Front‑panel LED indicators: ‑ Green OK: Module self‑test passed ‑ Red FAULT: Hardware / configuration / remote‑link fault ‑ XMIT: Expansion‑bus transmit activity ‑ RECV: Expansion‑bus receive activity
Installation & Wiring Requirements
- Power‑off entire rack before installation or replacement. Hot‑swap is not allowed. Apply ESD protection during module handling.
- Insert IC697BEM721 into free slot of Series 90‑70 main‑rack backplane and fasten module latch. Connect qualified 50‑pin parallel expansion bus cable between BEM721 and remote‑rack IC697BEM731 modules.
- Cable installation comply with manual GFK‑0366. Separate expansion bus cables from high‑power high‑voltage wiring. Reliable protective‑ground connection is mandatory.
- After replacement: Power‑on rack power, check front‑panel LED indicators. Download hardware configuration, define remote‑rack slot layout. Verify all I/O signals from every remote expansion rack. Simulate cable disconnection to check fault‑reporting behavior.
- Replacement note: Confirm total main‑rack backplane power budget. Check 50‑pin cable integrity and pin definition. Full‑system commissioning test is mandatory before putting into service.






Reviews