Description
Hardware & Electrical Specifications
‑ Model: IC698PSA100 ‑ Part Number: IC698PSA100 ‑ Module Type: PACSystems RX7i Rack Power Supply Module, occupies Slot 0 (far‑left slot) of RX7i chassis ‑ Mounting: RX7i main chassis slot 0 only ‑ Input specifications: • Nominal AC input: 120/240 VAC; operating range: 85‑264 VAC, 47‑63 Hz • Nominal DC input: 125 VDC; operating range: 100‑150 VDC • Max input power: 150 W; power factor ≥0.99 (90‑260 VAC) • Cold‑start inrush current: 30 A @115 VAC, 60 A @230 VAC ‑ Output specifications (total combined 100 W max): • +5 VDC: 4.875‑5.25 V, 0‑20 A • +12 VDC: 11.64‑12.6 V, 0‑2 A • −12 VDC: −12.6‑‑11.64 V, 0‑1 A • Ripple noise: < 60 mV peak‑to‑peak ‑ Hold‑up / Ride‑through: 5 ms minimum hold‑up; 15 ms minimum ride‑through at full‑load ‑ Isolation: 1500 VDC isolation between input and all output rails ‑ Protection features: Over‑current, over‑voltage, over‑temperature and short‑circuit protection ‑ Redundancy capability: Parallel redundant power‑supply operation supported ‑ Front‑panel control: Logic‑level on/off switch (does not cut off mains input) ‑ Diagnostics: Front‑panel LED status indicators; power‑fail status signal to VME backplane ‑ PCB treatment: Standard non‑conformal coated; revision suffix A‑N denote hardware iteration upgrades ‑ Compatibility note: Compatible with all RX7i CPU and I/O modules. Calculate total rack load before commissioning, must not exceed 100 W aggregate output rating. Hot‑swap prohibited. After replacement, verify input voltage, measure backplane output voltages, confirm all modules boot‑up normally; validate redundant operation if parallel configuration is used.
Environmental Specifications
‑ Operating temperature: 0 ℃ ~ +60 ℃; derate output power above +50 ℃ ‑ Storage temperature: −40 ℃ ~ +85 ℃ ‑ Relative humidity: 5%‑95% non‑condensing ‑ Installation location: Indoor control cabinet, IP20 protection class ‑ EMC compliance: IEC 61000‑6‑2 ‑ Certifications: CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight: approx 1.5 kg ‑ Dimension: RX7i standard single‑slot VME module form‑factor
Main Functions
- Converts universal AC/DC field input into multi‑rail regulated backplane power for all RX7i modules within chassis. Provides power‑fail sequencing signal to CPU for safe data saving before power collapse.
- Supports parallel redundant power‑supply architecture to improve system availability for critical control applications. Active PFC reduces mains harmonic distortion.
- Front‑panel LED indicators: ‑ PWR OK: DC output rails within normal operating range ‑ FAULT: Over‑voltage, over‑current, over‑temperature, short‑circuit or input power failure
Installation & Wiring Requirements
- Cut off AC/DC field input power before installation or replacement. Hot‑swap is not permitted. Apply ESD protection during module handling.
- Insert IC698PSA100 into slot 0 (far‑left dedicated power‑supply slot) of RX7i chassis and fasten module latch. For redundant configuration, install second PSA100 into slot 0 of second rack with proper load sharing setup.
- Field input wiring comply with manual GFK‑2223. Use appropriate wire gauge; install external upstream over‑current protection. Reliable protective‑ground connection for rack chassis is mandatory.
- After replacement: Restore field input power, observe front‑panel LED status. Measure +5 V, ±12 V backplane voltages. Verify CPU, communication and I/O modules boot and run stable. For redundant power setup, test fault simulation of one power‑supply unit.
- Replacement note: Always calculate total rack power consumption before adding new modules to avoid overloading power‑supply unit. Full‑system commissioning test is mandatory before putting into service.