IS200AEADH4ADA is intelligent analog & RTD input module for GE Mark VIe Speedtronic gas / steam turbine control system. It features 4 channels configurable analog input plus 4‑channel Pt100/Pt1000 RTD temperature input, supports 4‑20 mA / ±10 V signal from field transmitters and thermal resistance sensors. On‑board DSP completes signal conditioning, A‑D conversion, engineering‑unit scaling and channel diagnosis. It communicates with main controller via IONet backplane Ethernet bus, supports HART pass‑through function. Conformal coated PCB for heavy‑duty power‑plant environment, provides process pressure, flow and bearing temperature measuring data for turbine control & protection logic. Product status: Obsolete, spare‑part only supply available。

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware & Electrical Specifications

  • Model:IS200AEADH4ADA
  • Part Number:IS200AEADH4ADA
  • Module Type:Analog‑RTD Input Module
  • Rack slot:Single‑slot 3U module for Mark VIe I/O rack
  • Power supply:+5 VDC from rack backplane, typical power consumption 3.5 W
  • Analog input:4 channels, configurable 4‑20 mA / ±10 V DC; 16‑bit ADC resolution
  • RTD input:4‑channel 3‑wire Pt100 / Pt1000 thermal resistance input
  • Communication:IONet 100 Mbps full‑duplex Ethernet backplane bus, HART pass‑through compatible
  • Measuring accuracy:AI ±0.1% full‑scale; RTD ±0.5 ℃ full range
  • Galvanic isolation:500 V DC channel‑to‑channel, channel‑to‑backplane isolation
  • Scan rate:10 ms per channel typical update rate
  • On‑board protection:ESD protection, over‑range detection, open‑wire / short‑circuit diagnosis for each channel, conformal coated PCB
  • Compatibility note:Cannot run standalone; must match Mark VIe controller hardware, terminal base IS200TBAIH series; firmware version matching required after replacement.

Environmental Specifications

  • Operating temperature:‑30 ℃ ~ +65 ℃
  • Storage temperature:‑40 ℃ ~ +85 ℃
  • Relative humidity:5%‑95% non‑condensing
  • Installation location:Inside turbine control cabinet rack
  • EMC compliance:IEC 61000‑6‑2
  • Certifications:CE

Mechanical Data

  • Weight:approx 1.10 kg
  • Dimension:168 mm × 148 mm × 55 mm
  • Connection:VME‑style backplane edge connector; mate with IS200TBAIH terminal base via ribbon cable
  • Handling note:ESD‑sensitive assembly, anti‑static operation mandatory
  • Recommended wire cross‑section:0.75 mm²‑2.5 mm² copper for field signal terminals
  • Terminal tightening torque:0.6‑1.0 N·m

Main Functions

  1. Acquire 4‑20 mA / voltage analog signals from pressure, flow and level transmitters.
  2. Excitation and sampling for 3‑wire Pt100 / Pt1000 RTD sensors for bearing & lube‑oil temperature measurement.
  3. Local DSP performs A‑D conversion, signal filtering, linearization and engineering‑unit scaling, reduce CPU load.
  4. HART pass‑through for remote parameter access to HART‑capable field transmitters.
  5. Per‑channel diagnosis: open‑wire, short‑circuit, over‑range fault detection, send alarm status to controller.
  6. IONet Ethernet backplane communication to exchange measuring data and fault status with main controller.
  7. LED status indication:
    • Green LED:Module power‑on and healthy
    • Yellow LED:IONet bus communication active
    • Red LED:Channel fault / communication loss / module hardware fault

Installation & Wiring Requirements

  1. Cut off rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB module.
  2. Insert module fully into rack slot, lock ejector levers; ensure reliable connection with corresponding terminal base ribbon cable.
  3. Field wiring strictly follow GE Mark VIe wiring drawing; separate weak‑signal sensor cables from high‑power cables for noise suppression.
  4. Complete protective grounding according to GE Speedtronic system specification.
  5. After replacement, verify IONet link status, download module configuration, perform channel calibration; validate measuring values before commissioning.
  6. Replacement note: firmware compatibility check and full‑channel function test are mandatory after swap.