Description
Hardware & Electrical Specifications
- Model:IS200AEADH4ADA
- Part Number:IS200AEADH4ADA
- Module Type:Analog‑RTD Input Module
- Rack slot:Single‑slot 3U module for Mark VIe I/O rack
- Power supply:+5 VDC from rack backplane, typical power consumption 3.5 W
- Analog input:4 channels, configurable 4‑20 mA / ±10 V DC; 16‑bit ADC resolution
- RTD input:4‑channel 3‑wire Pt100 / Pt1000 thermal resistance input
- Communication:IONet 100 Mbps full‑duplex Ethernet backplane bus, HART pass‑through compatible
- Measuring accuracy:AI ±0.1% full‑scale; RTD ±0.5 ℃ full range
- Galvanic isolation:500 V DC channel‑to‑channel, channel‑to‑backplane isolation
- Scan rate:10 ms per channel typical update rate
- On‑board protection:ESD protection, over‑range detection, open‑wire / short‑circuit diagnosis for each channel, conformal coated PCB
- Compatibility note:Cannot run standalone; must match Mark VIe controller hardware, terminal base IS200TBAIH series; firmware version matching required after replacement.
Environmental Specifications
- Operating temperature:‑30 ℃ ~ +65 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Inside turbine control cabinet rack
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Weight:approx 1.10 kg
- Dimension:168 mm × 148 mm × 55 mm
- Connection:VME‑style backplane edge connector; mate with IS200TBAIH terminal base via ribbon cable
- Handling note:ESD‑sensitive assembly, anti‑static operation mandatory
- Recommended wire cross‑section:0.75 mm²‑2.5 mm² copper for field signal terminals
- Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Acquire 4‑20 mA / voltage analog signals from pressure, flow and level transmitters.
- Excitation and sampling for 3‑wire Pt100 / Pt1000 RTD sensors for bearing & lube‑oil temperature measurement.
- Local DSP performs A‑D conversion, signal filtering, linearization and engineering‑unit scaling, reduce CPU load.
- HART pass‑through for remote parameter access to HART‑capable field transmitters.
- Per‑channel diagnosis: open‑wire, short‑circuit, over‑range fault detection, send alarm status to controller.
- IONet Ethernet backplane communication to exchange measuring data and fault status with main controller.
- LED status indication:
- Green LED:Module power‑on and healthy
- Yellow LED:IONet bus communication active
- Red LED:Channel fault / communication loss / module hardware fault
Installation & Wiring Requirements
- Cut off rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB module.
- Insert module fully into rack slot, lock ejector levers; ensure reliable connection with corresponding terminal base ribbon cable.
- Field wiring strictly follow GE Mark VIe wiring drawing; separate weak‑signal sensor cables from high‑power cables for noise suppression.
- Complete protective grounding according to GE Speedtronic system specification.
- After replacement, verify IONet link status, download module configuration, perform channel calibration; validate measuring values before commissioning.
- Replacement note: firmware compatibility check and full‑channel function test are mandatory after swap.