Description
Hardware & Electrical Specifications
- Model:IS200DTAIH1ABB
- Part Number:IS200DTAIH1ABB
- Module Type:Simplex Analog Input‑Output Terminal Board
- Mounting:Plastic bracket, DIN‑rail installation inside control cabinet
- Power supply:Auxiliary 24 V DC from system rack
- Analog Input:10 channels, configurable 0‑10 V / 4‑20 mA via jumper settings
- Analog Output:2 channels, standard 0‑20 mA; one channel configurable for 0‑200 mA by jumper modification
- Connector:JR1 37‑pin locking connector (connects to corresponding I/O core board by ribbon cable)
- Terminals:TB1 48‑position screw terminal block; 43/44 terminals assigned for signal common ground(SCOM)
- Jumper resource:21 groups of jumper switches for channel signal‑mode configuration
- PCB treatment:Conformal coated for anti‑dust and anti‑moisture
- On‑board protection:ESD protection, surge suppression, filter circuit for field signal
- Compatibility note:Cannot run standalone; must mate with matching Mark VI analog I/O controller board; jumper configuration must match field signal type after replacement.
Environmental Specifications
- Operating temperature:‑30 ℃ ~ +65 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Indoor turbine control cabinet
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Weight:approx 1.20 kg
- Dimension:200 mm × 145 mm × 55 mm
- Handling note:ESD‑sensitive PCB, anti‑static operation mandatory
- Recommended wire cross‑section:0.75 mm²‑2.5 mm² shielded twisted‑pair copper cable for field wiring
- Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Terminate field analog signals from pressure, flow and other process transmitters via screw terminals.
- Route field analog input signals to matched I/O core board through 37‑pin ribbon connector.
- Convert analog output signals from controller board to field‑side current‑type control signals for actuators.
- On‑board jumpers configure each channel for voltage‑mode or current‑mode signal according to site requirements.
- Provide signal common ground terminal for field‑side shielding connection.
- Hardware circuit filtering and surge suppression to improve anti‑interference capability for long‑distance field wiring.
- LED status indication:
- Green LED:Terminal board auxiliary power normal
- Yellow LED:Signal channel active
- Red LED:Over‑range / external short‑circuit fault on field channel
Installation & Wiring Requirements
- Cut off rack power supply before replacement. Hot‑swap is forbidden. Take anti‑static measures when handling PCB board.
- Fix the plastic DIN‑rail bracket firmly; ensure reliable locking of JR1 37‑pin connector.
- Set on‑board jumpers strictly according to field signal type (voltage / current) before field wiring.
- Field wiring adopts shielded twisted‑pair; separate analog signal cables from high‑power cables to reduce interference. Connect shielding wire to SCOM ground terminal with shortest wire length.
- Complete protective grounding following GE Mark VI system specification.
- After replacement: double‑check jumper configuration, verify each channel input‑output value, confirm no short‑circuit fault before commissioning.
- Replacement note: Jumper setting must be consistent with original configuration; mis‑jumper will lead to signal measurement error or hardware damage.