Description
Hardware & Electrical Specifications
- Model:IS200ERIOH1AAA
- Part Number:IS200ERIOH1AAA
- Module Type:Exciter‑Regulator I/O Board (ERIO)
- Form factor:Single‑slot double‑height 6U VME plug‑in board
- Power supply:+5 V DC from exciter backplane, typical power consumption 10 W
- Backplane interface:Dual 96‑pin P1/P2 VME back‑plane connectors
- Front‑panel connectors:2‑pcs 25‑pin D‑Sub (connect to EPCT / ECTBG2 terminal boards); 9‑pin TEST diagnostic port
- Signal processing:Condition PT/CT analog sampling, digital interlock & protection I/O for excitation loop
- Isolation:Channel‑to‑backplane galvanic isolation, 1500 V DC isolation rating
- Scan rate:Typical 5 ms signal update for AVR closed‑loop control
- PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance
- On‑board protection:ESD protection, surge suppression, hardware watchdog circuit
- Compatibility note:Cannot run standalone; must match EX2100 system hardware revision; simplex fits ERBP rack; redundant system installs on ERRB rack; full‑signal‑loop test required after replacement。
Environmental Specifications
- Operating temperature:‑40 ℃ ~ +70 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Excitation control cabinet ERBP / ERRB rack
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Weight:approx 1.0 kg
- Dimension:340 mm × 216 mm × 55 mm
- Handling note:ESD‑sensitive PCB, anti‑static wrist‑strap mandatory during handling
- Recommended wire cross‑section:0.75‑2.5 mm² shielded twisted‑pair copper cable for D‑Sub interconnection cables
- Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Condition and route PT/CT generator voltage & current sampling signals from EPCT terminal board to DSPX controller for AVR regulation calculation。
- Receive external discrete interlock signals (breaker status, permit‑to‑run, trip commands) from ECTBG2 terminal board.
- Interface internal system I/O signals to ERDD dynamic‑discharge board and EROC option board.
- Route excitation control output, trip‑logic and alarm signals between back‑plane bus and field‑side terminal assemblies.
- Front‑panel TEST port supports real‑time signal monitoring for commissioning and troubleshooting.
- On‑board hardware self‑diagnosis: detect power failure, signal‑chain abnormality, VME‑bus communication loss, report fault status to main controller.
- Front‑panel LED status indication:
- Green LED:Board power supply normal
- Yellow LED:VME‑bus communication active
- Red LED:Signal‑chain fault / hardware failure
Installation & Wiring Requirements
- Cut off excitation rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Insert module fully into designated ERBP / ERRB rack slot, lock ejector levers to guarantee reliable back‑plane contact.
- Connect front‑panel D‑Sub cables to EPCT / ECTBG2 terminal boards strictly follow GE EX2100 wiring manual; separate weak‑signal cables from high‑power cables.
- Complete protective grounding according to GE Speedtronic system specification.
- After replacement: verify VME‑bus link status, check PT/CT sampling value, validate interlock‑signal response, perform full excitation‑loop static test before commissioning.
- Replacement note: Confirm hardware revision matches system simplex/redundant architecture; full‑function signal‑loop test is mandatory after swap.