Description
Hardware & Electrical Specifications
- Model:IS200EROCH1ABB
- Part Number:IS200EROCH1ABB
- Module Type:Exciter‑Regulator Options Card (EROC)
- Form factor:Single‑slot plug‑in board for ERBP / ERRB rack
- Power supply:+5 V / 70 V auxiliary power from exciter backplane
- Serial interface:RS‑232C keypad port on front‑panel; baud‑rate range 1200‑38400 bps
- Tool port:9‑pin RS‑232 diagnostic connector for laptop commissioning
- Signal input:Ground‑detector alarm, detector fault, diode‑fault monitoring input terminals
- Backplane interface:Dual‑connector ISBus internal communication bus
- PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance
- On‑board protection:ESD protection, surge suppression, isolated power circuit for serial channel
- Compatibility note:Cannot run standalone; dedicated for EX2100 excitation system; for redundant architecture, keypad must connect to M1‑side EROC; full‑function test required after replacement。
Environmental Specifications
- Operating temperature:‑30 ℃ ~ +65 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Excitation control cabinet ERBP / ERRB rack
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Weight:approx 0.35 kg
- Dimension:228 mm × 152 mm × 38 mm
- Handling note:ESD‑sensitive PCB, anti‑static wrist‑strap mandatory during handling
- Recommended wire cross‑section:0.75‑2.5 mm² copper cable for keypad and ground‑detector signal wiring
- Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- RS‑232 communication interface for local operator keypad, transmit keypad commands and return display data to DSPX controller。
- Signal conditioning for GE‑EGDM or third‑party field‑ground‑detector alarm, fault and diode‑monitor signals.
- Supply auxiliary 70 V DC power for external field‑side terminal assemblies.
- Front‑panel 9‑pin tool port for laptop‑based on‑site commissioning, parameter setting and fault troubleshooting.
- ISBus backplane duplex data exchange with DSPX, ERIO and other functional boards.
- On‑board self‑diagnosis: detect module power failure, serial‑port fault, input‑signal abnormality, report fault status to main controller.
- Front‑panel LED status indication:
- Green LED:Module power‑on normal
- Yellow LED:ISBus / serial‑port communication active
- Red LED:External detector fault / board hardware fault
Installation & Wiring Requirements
- Cut off excitation rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Insert module fully into designated ERBP / ERRB rack slot, ensure reliable back‑plane connector contact.
- For redundant system: keypad cable must connect to M1(ERBP) side EROC according to GE EX2100 manual; do not connect keypad to M2‑side board。
- Keypad, ground‑detector signal wiring strictly follow GE EX2100 wiring drawing; separate weak‑signal cables from high‑power cables.
- Complete protective grounding according to GE Speedtronic system specification.
- After replacement: verify keypad operation response, tool‑port communication, ground‑detector signal acquisition before commissioning.
- Replacement note: Confirm rack slot matches simplex / redundant architecture; full‑function test is mandatory after swap.

-300x300.jpg)