Description
Hardware & Electrical Specifications
- Model:IS200SAMBH1ABA
- Part Number:IS200SAMBH1ABA
- Module Type:SAMB Simplex Analog Multiplexer Terminal Board
- Mounting:DIN‑rail mounting bracket installed inside turbine control cabinet
- Power supply:+24 V DC auxiliary power supplied by I/O pack through ribbon cable
- Signal channels:Multi‑channel analog AI/AO signal multiplexing, support 4‑20 mA / 0‑10 V transducer signals
- Interface:Multi‑group screw terminal blocks for field wiring; high‑density IDC ribbon‑cable connector connecting to I/O pack
- Signal switching:Analog multiplexer switching time less than 10 μs
- PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance
- On‑board protection:ESD protection, surge suppression, EMI RC filter circuit for analog signal loops
- Compatibility note:Cannot run standalone; must match corresponding Mark VI / Mark VIe analog I/O pack; ribbon cable must be fastened reliably; full‑channel signal calibration test required after replacement。
Environmental Specifications
- Operating temperature:‑30 ℃ ~ +70 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Indoor turbine control cabinet
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Weight:approx 1.10 kg
- Dimension:231 mm × 143 mm × 55 mm
- Handling note:ESD‑sensitive PCB, anti‑static wrist‑strap mandatory during handling
- Recommended wire cross‑section:0.75‑2.5 mm² shielded twisted‑pair copper cable for field‑transducer wiring
- Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Provide screw‑terminal field termination for analog transmitters, valve position feedback and analog actuator control signals.
- Multiplex and route multi‑channel analog signals between field devices and I/O pack via high‑density ribbon‑cable interface.
- On‑board EMI filter suppress high‑frequency industrial interference for long‑distance field wiring.
- Signal conditioning and surge protection to improve measuring accuracy in high‑EMI power‑plant environment.
- Channel fault diagnosis: detect loop open‑circuit, short‑circuit fault, transmit fault status to main controller through I/O pack.
- LED status indication:
- Green LED:Terminal‑board auxiliary power normal
- Yellow LED:Ribbon‑cable link communication active
- Red LED:Field‑channel loop fault / link abnormal alarm
Installation & Wiring Requirements
- Cut off rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Secure DIN‑rail mounting bracket firmly; ensure IDC ribbon‑cable connector fully locked without loose contact.
- Field transducer wiring strictly follow GE Mark VI / Mark VIe wiring manual; analog signal cables must be shielded twisted‑pair and separated from high‑power cables; connect shield to dedicated ground terminal.
- Complete protective grounding according to GE Speedtronic system specification.
- After replacement: verify ribbon‑cable link status, calibrate each analog channel reading, validate transducer feedback before commissioning.
- Replacement note: TMR redundant system requires three‑set SAMB hardware consistency verification; full‑channel analog function test is mandatory after swap.