Description
Hardware & Electrical Specifications
- Model:IS200STCIH6AED
- Part Number:IS200STCIH6AED
- Module Type:STCI Simplex Contact‑Input Terminal Board
- Mounting:DIN‑rail bracket or flat panel mounting inside turbine cabinet深圳长欣自…
- Power supply:+24 V DC auxiliary power supplied by PAIC I/O pack
- Input channels:24 optically‑isolated discrete input channels; support dry‑contact / wet‑contact 24‑48‑125 VDC mode configurable by hardware jumpers深圳长欣自…
- Galvanic isolation:Opto‑coupler isolation, 1500 V DC isolation rating
- Response time:Typical ≤1 ms for discrete interlock signals
- Interface:Green screw terminal blocks for field wiring; 37‑pin high‑density IDC ribbon‑cable connector connecting to PAIC I/O pack深圳长欣自…
- PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance
- On‑board protection:ESD protection, surge suppression, input transient absorption circuit
- Compatibility note:Cannot run standalone; must match PAIC discrete I/O pack; jumper wet‑contact voltage setting must restore exactly after replacement; simplex‑only hardware, not for TMR safety trip loops; full‑channel contact‑input function test required after replacement深圳长欣自…。
Environmental Specifications
- Operating temperature:‑40 ℃ ~ +70 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Indoor turbine control cabinet
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Weight:approx 0.42 kg
- Dimension:172 mm ×146 mm ×40 mm
- Handling note:ESD‑sensitive PCB, anti‑static wrist‑strap mandatory during handling
- Recommended wire cross‑section:0.75‑2.5 mm² shielded twisted‑pair copper cable for field‑contact wiring
- Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Screw‑terminal field termination for field discrete dry‑contact / wet‑contact signals: breaker status, valve limit position, auxiliary equipment running feedback, pressure‑switch interlock contacts.
- Optical isolation between plant field wiring and internal control logic, suppress ground‑loop noise and industrial surge interference.
- Convert contact open‑close status into digital logic signals, transmit to PAIC I/O pack via ribbon‑cable link for turbine logic processing.
- On‑board channel fault diagnosis: detect field‑loop open‑circuit fault, report fault status to main controller.
- On‑board self‑diagnosis: detect terminal‑board auxiliary power loss and ribbon‑cable link failure.
- LED status indication:
- Green LED:Terminal‑board auxiliary power normal
- Yellow LED:Ribbon‑cable link communication active
- Red LED:Field‑channel fault / link communication loss alarm
Installation & Wiring Requirements
- Cut off rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Secure DIN‑rail mounting bracket firmly; ensure 37‑pin IDC ribbon‑cable connector fully locked without loose contact.
- Restore on‑board jumper setting (dry‑contact / wet‑contact voltage mode) strictly consistent with original configuration before field wiring.
- Field contact‑signal wiring strictly follow GE Speedtronic wiring manual; discrete signal cables adopt shielded twisted‑pair, separate from high‑power cables; connect shielding to dedicated ground terminal.
- Complete protective grounding according to GE Speedtronic system specification.
- After replacement: verify ribbon‑cable link status, test each channel open‑close response, validate interlock‑signal logic before commissioning.
- Replacement note: This hardware is simplex‑only, cannot apply for TMR triple‑redundant safety trip loops; full‑channel discrete‑input function test mandatory after swap.





-1-1-300x300.jpg)