Description
Hardware & Electrical Specifications
- Model:IS200TBCIH1CCD
- Part Number:IS200TBCIH1CCD
- Module Type:TBCI TMR‑capable Contact‑Input Terminal Board
- Mounting:DIN‑rail or cabinet panel mounting inside turbine control cabinet
- Power supply:+24 V DC auxiliary power supplied by PADC I/O pack
- Input channels:24 contact input channels, support dry‑contact and 24‑125 VDC wet‑contact excitation modeKongJiang …
- Isolation:Group‑based galvanic isolation design, isolation rating 1500 V DC
- Response time:Typical ≤1 ms for safety interlock signals
- Interface:Two barrier‑type screw terminal blocks for field wiring; three high‑density IDC ribbon‑cable connectors for PADC I/O pack interconnection
- PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance
- On‑board protection:ESD protection, MOV surge suppression, transient absorption circuit for contact loops
- Compatibility note:Cannot run standalone; must match PADC discrete I/O pack; TMR system requires three identical TBCI boards; full‑channel contact‑input simulation test mandatory after replacement.
Environmental Specifications
- Operating temperature:‑30 ℃ ~ +65 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Indoor turbine control cabinet
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Weight:approx 1.30 kg
- Dimension:330 mm ×102 mm ×48 mm
- Handling note:ESD‑sensitive PCB, anti‑static wrist‑strap mandatory during handling
- Recommended wire cross‑section:0.75‑2.5 mm² shielded twisted‑pair copper cable for field‑contact wiring
- Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Screw‑terminal field termination for turbine discrete contact signals: breaker auxiliary status, valve limit position, auxiliary equipment running feedback, safety interlock contact signals.
- Group galvanic isolation between plant field wiring and control logic side, suppress ground‑loop noise and industrial surge interference.
- Convert contact open‑close status into digital logic signals, transmit to PADC I/O pack through triple ribbon‑cable interface for turbine sequence and protection voting‑logic processing.
- Built‑in surge and transient suppression for long‑distance field wiring under high‑EMI turbine‑hall environment.
- On‑board channel fault diagnosis: detect field‑loop open‑circuit fault, report fault status to main controller.
- On‑board self‑diagnosis: detect terminal‑board auxiliary power loss and ribbon‑cable link failure.
- LED status indication:
- Green LED:Terminal‑board auxiliary power normal
- Yellow LED:Ribbon‑cable link communication active
- Red LED:Field‑channel fault / link communication loss alarm
Installation & Wiring Requirements
- Cut off rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Secure mounting bracket firmly; ensure three IDC ribbon‑cable connectors fully locked without loose contact.
- Field contact‑signal wiring strictly follow GE Speedtronic wiring manual; safety‑related discrete signal cables must adopt shielded twisted‑pair, strictly separated from high‑power cables; connect shielding to dedicated ground terminal.
- Complete protective grounding according to GE Speedtronic system specification.
- After replacement: verify ribbon‑cable link status, test each channel open‑close response, validate protection‑interlock logic before commissioning.
- Replacement note: For TMR triple‑redundant safety‑loop application, three‑set TBCI hardware consistency must be verified; full safety‑signal simulation test is mandatory after swap