Description
Hardware & Electrical Specifications
- Model:IS200TDBSH2ACC
- Part Number:IS200TDBSH2ACC
- Module Type:TDBS TMR‑capable Discrete‑Input Relay‑Output Terminal Board
- Mounting:DIN‑rail or cabinet panel mounting inside turbine control cabinet
- Power supply:+24 V DC auxiliary power supplied by PADC I/O pack
- Input channels:24 group‑isolated discrete‑input channels; support dry‑contact / 24‑125 VDC wet‑contact mode
- Output channels:12‑channel Form‑C SPDT relay outputs
- Relay contact rating:5 A @250 VAC / 30 VDC resistive load
- Isolation:Group‑based galvanic isolation, isolation rating 1500 V DC
- Response time:Input ≤1 ms; relay output ≤10 ms
- Interface:Barrier‑type screw terminal blocks for field wiring; multi‑channel high‑density IDC ribbon‑cable connectors for PADC I/O pack interconnection
- PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance
- On‑board protection:ESD protection, MOV surge suppression, transient absorption circuit for each signal loop
- Compatibility note:Cannot run standalone; must match PADC I/O pack; TMR system requires three identical TDBS boards; full‑channel input‑output simulation test mandatory after replacement.
Environmental Specifications
- Operating temperature:‑40 ℃ ~ +70 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Indoor turbine control cabinet
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Weight:approx 1.20 kg
- Dimension:330 mm ×178 mm ×48 mm
- Handling note:ESD‑sensitive PCB, anti‑static wrist‑strap mandatory during handling
- Recommended wire cross‑section:0.75‑2.5 mm² shielded twisted‑pair copper cable for field‑contact and actuator wiring
- Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Screw‑terminal field termination for field discrete signals: breaker auxiliary contacts, valve limit switches, pump‑fan running feedback, safety interlock contact signals; relay output for solenoid valves, auxiliary equipment control and partial trip logic drive.
- Group galvanic isolation between plant field wiring and control logic side, suppress ground‑loop noise and industrial surge interference.
- Convert contact open‑close status into digital logic signals, transmit to PADC I/O pack through multi‑ribbon‑cable interface for turbine sequence and protection voting‑logic processing; receive logic commands from I/O pack and drive on‑board relay outputs.
- Built‑in surge and transient suppression for long‑distance field wiring under high‑EMI turbine‑hall environment.
- On‑board channel fault diagnosis: detect field‑loop open‑circuit fault, report fault status to main controller.
- On‑board self‑diagnosis: detect terminal‑board auxiliary power loss and ribbon‑cable link failure.
- LED status indication:
- Green LED:Terminal‑board auxiliary power normal
- Yellow LED:Ribbon‑cable link communication active
- Red LED:Field‑channel fault / link communication loss alarm
Installation & Wiring Requirements
- Cut off rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Secure mounting bracket firmly; ensure multi‑group IDC ribbon‑cable connectors fully locked without loose contact.
- Field signal wiring strictly follow GE Speedtronic wiring manual; safety‑related discrete signal cables must adopt shielded twisted‑pair, strictly separated from high‑power cables; connect shielding to dedicated ground terminal.
- Complete protective grounding according to GE Speedtronic system specification.
- After replacement: verify ribbon‑cable link status, test each input‑channel open‑close response and each relay‑output action, validate protection‑interlock logic before commissioning.
- Replacement note: For TMR triple‑redundant safety‑loop application, three‑set TDBS hardware consistency must be verified; full safety‑signal input‑output simulation test is mandatory after swap.




-300x300.jpg)
-1-300x300.jpg)
Reviews