Description
Hardware & Electrical Specifications
- Model:IS200TDBTH6ABC
- Part Number:IS200TDBTH6ABC
- Module Type:TDBT TMR‑Capable Discrete‑Input / Transistor‑Output Terminal Board
- Mounting:DIN‑rail or cabinet panel mounting inside turbine control cabinet
- Power supply:+24 V DC auxiliary power supplied by PADC I/O pack
- Input channels:24 optically‑isolated discrete input channels; support dry‑contact / 24‑125 VDC wet‑contact mode configurable by on‑board jumpers
- Output channels:6‑channel NPN sink‑type transistor outputs, organized into 3 redundant channel‑pairs for TMR voting trip logic; 5‑30 VDC load voltage, max 100 mA per channel
- Isolation:Opto‑coupler galvanic isolation, isolation rating 1500 V DC
- Response time:Input ≤1 ms; transistor output ≤0.8 μs for safety trip commands
- Interface:Barrier screw terminal blocks for field wiring; three IDC ribbon‑cable connectors for PADC I/O pack interconnection
- PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance
- On‑board protection:ESD protection, MOV surge suppression, over‑current limiting for each output channel
- Compatibility note:Cannot run standalone; must match PADC I/O pack; TMR system requires three identical TDBT boards; full‑channel input‑output simulation test mandatory after replacement.
Environmental Specifications
- Operating temperature:‑40 ℃ ~ +70 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Indoor turbine control cabinet
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Weight:approx 1.30 kg
- Dimension:330 mm × 178 mm × 55 mm
- Handling note:ESD‑sensitive PCB; high‑speed safety‑output circuit, anti‑static wrist‑strap mandatory during handling
- Recommended wire cross‑section:0.75‑2.5 mm² shielded twisted‑pair copper cable for field‑contact and actuator wiring
- Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Screw‑terminal field termination for discrete status signals: breaker auxiliary contacts, valve limit switches, pump‑fan running feedback, safety interlock contact signals; transistor output drives field solenoid valves and safety trip‑circuit loads.
- Optical galvanic isolation between plant field wiring and control logic side, suppress ground‑loop noise and industrial surge interference.
- Convert contact open‑close status into digital logic and send to PADC I/O pack; receive trip/control commands from I/O pack and drive on‑board sink‑type transistor outputs for turbine protection voting‑logic processing.
- Per‑channel over‑current limiting protection prevents field short‑circuit damage to I/O pack internal circuits.
- On‑board channel self‑diagnosis: detect field‑loop open‑circuit fault, report fault status to main controller.
- On‑board self‑diagnosis: detect terminal‑board auxiliary power loss and ribbon‑cable link failure.
- LED status indication:
- Green LED:Terminal‑board auxiliary power normal
- Yellow LED:Ribbon‑cable link communication active
- Red LED:Field‑channel fault / link communication loss alarm
Installation & Wiring Requirements
- Cut off rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Secure mounting bracket firmly; ensure three IDC ribbon‑cable connectors fully locked without loose contact.
- Restore on‑board jumper configuration (dry‑contact / wet‑contact voltage mode) strictly consistent with original settings before field wiring.
- Safety‑related signal wiring strictly follow GE Speedtronic wiring manual; adopt shielded twisted‑pair cables, strictly separated from high‑power cables; connect shielding to dedicated ground terminal.
- Complete protective grounding according to GE Speedtronic system specification.
- After replacement: verify ribbon‑cable link status, test each input‑channel open‑close response and each transistor‑output driving capability, validate turbine safety‑trip‑logic response before commissioning.
- Replacement note: For TMR triple‑redundant safety‑loop application, three‑set TDBT hardware consistency must be verified; full safety‑signal input‑output simulation test mandatory after swap.