Hardware & Electrical Specifications
- Model:IS200TPROH1C
- Part Number:IS200TPROH1C
- Module Type:TPRO TMR‑capable Protection Terminal Board
- Mounting:Cabinet panel mounting inside turbine control cabinet
- Power supply:+24 V DC auxiliary power supplied by PPRO I/O packs
- Input channels:Multi‑channel protection discrete input channels, support dry‑contact and 24‑125 VDC wet‑contact signal
- Isolation:Built‑in isolation transformers, high galvanic isolation rating
- Response time:Typical ≤1 ms for safety trip‑signal response
- Interface:Two barrier‑type removable screw terminal blocks for field wiring; multiple 37‑pin IDC ribbon‑cable connectors for PPRO I/O pack interconnection
- PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance
- On‑board protection:ESD protection, surge suppression, transient absorption circuit for safety‑signal loops
- Compatibility note:Cannot run standalone; must match PPRO protection I/O pack; TMR system requires three‑set hardware consistency verification; full protection‑loop simulation test mandatory after replacement.
Environmental Specifications
- Operating temperature:‑40 ℃ ~ +70 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Indoor turbine control cabinet
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Weight:approx 1.40 kg
- Dimension:330 mm × 178 mm × 55 mm
- Handling note:ESD‑sensitive PCB, safety‑protection signal circuit, anti‑static wrist‑strap mandatory during handling
- Recommended wire cross‑section:0.75‑2.5 mm² shielded twisted‑pair copper cable for field protection‑signal wiring
- Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Removable barrier screw‑terminal field termination for turbine critical safety protection signals: backup overspeed trip, vibration trip, low‑oil‑pressure trip, ESD emergency‑shutdown contact signals.
- Built‑in isolation transformers provide galvanic isolation between plant field wiring and control logic side, suppress ground‑loop noise and industrial surge interference.
- Condition protection discrete signals and transmit to three PPRO I/O packs via multi‑ribbon‑cable interface for turbine protection voting‑logic processing.
- Surge and transient suppression for long‑distance field wiring under high‑EMI turbine‑hall environment.
- On‑board channel self‑diagnosis: detect field‑loop open‑circuit / abnormal fault, report fault status to turbine main controller.
- On‑board self‑diagnosis: detect terminal‑board auxiliary power loss and ribbon‑cable link failure.
- LED status indication:
- Green LED:Terminal‑board auxiliary power normal
- Yellow LED:Ribbon‑cable link communication active
- Red LED:Field‑protection‑channel fault / link communication loss alarm
Installation & Wiring Requirements
- Cut off rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Secure panel mounting firmly; ensure all 37‑pin IDC ribbon‑cable connectors fully locked without loose contact.
- Field safety‑protection‑signal wiring strictly follow GE Speedtronic Mark VI wiring manual; safety‑related signal cables adopt shielded twisted‑pair, strictly separated from high‑power cables; connect shielding to dedicated ground terminal.
- Complete protective grounding according to GE Speedtronic system specification.
- After replacement: verify ribbon‑cable link status, simulate each protection trip‑signal input, validate turbine trip‑logic response before commissioning.
- Replacement note: For TMR triple‑redundant safety‑loop application, three‑set TPRO channel consistency must be verified; full safety‑protection‑loop simulation test is mandatory after swap.