Description
Hardware & Electrical Specifications
- Model:IS200TREAH2AED
- Part Number:IS200TREAH2AED
- Module Type:TREA Emergency Trip Terminal Board
- Mounting:Cabinet panel mounting inside turbine control cabinet
- Power supply:+24 VDC auxiliary power supplied by PPRO I/O packs
- Input channels:Multi‑channel discrete contact inputs; support dry‑contact / 24‑125 VDC wet‑contact; multi‑channel MPU magnetic‑pickup pulse inputs for overspeed detection
- Output channels:Hardware trip relay outputs for emergency trip circuit drive
- Isolation:Group‑based galvanic isolation, isolation rating 1500 V DC
- Trip response time:Hardware trip action within 5 ms for safety protection signals
- Interface:Removable barrier‑type screw terminal blocks for field wiring; multiple multi‑pin IDC ribbon‑cable connectors for PPRO I/O pack interconnection
- PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance
- On‑board protection:ESD protection, MOV surge suppression, transient absorption circuit for safety‑signal loops
- Compatibility note:Cannot run standalone; must match Mark VIe PPRO protection I/O pack; TMR system requires three identical TREA boards; full emergency‑trip simulation test mandatory after replacement.
Environmental Specifications
- Operating temperature:‑30 ℃ ~ +65 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Indoor turbine control cabinet
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Weight:approx 1.40 kg
- Dimension:330 mm × 178 mm × 55 mm
- Handling note:ESD‑sensitive PCB; safety‑critical overspeed‑detection circuit, anti‑static wrist‑strap mandatory during handling
- Recommended wire cross‑section:0.75‑2.5 mm² shielded twisted‑pair copper cable for field safety‑signal wiring
- Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Removable barrier screw‑terminal field termination for turbine critical safety signals: MPU overspeed pulse signals, ESD emergency‑shutdown contacts, low‑oil‑pressure trip, high‑vibration trip and other hard‑wired protection contact signals.
- Group galvanic isolation between plant field wiring and control logic side, suppress ground‑loop noise and industrial surge interference in turbine‑hall environment.
- Condition speed pulse and discrete trip signals, transmit to three PPRO I/O packs via multi‑ribbon‑cable interface; realize hardware‑level 2‑out‑of‑3 voting logic and drive trip relay outputs for turbine emergency shutdown.
- On‑board channel fault diagnosis: detect MPU sensor open‑circuit / short‑circuit, field‑loop abnormal fault, report fault status to main controller.
- On‑board self‑diagnosis: detect auxiliary power loss and ribbon‑cable link failure.
- LED status indication:
- Green LED:Terminal‑board auxiliary power normal
- Yellow LED:Ribbon‑cable link communication active
- Red LED:Field‑channel fault / overspeed condition / trip‑active / link communication loss alarm
Installation & Wiring Requirements
- Cut off rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Secure panel mounting firmly; ensure all multi‑pin IDC ribbon‑cable connectors fully locked without loose contact.
- Field safety‑signal wiring strictly follow GE Speedtronic Mark VIe wiring manual; safety‑related signal cables must adopt shielded twisted‑pair, strictly separated from high‑power cables; connect shielding to dedicated ground terminal.
- Complete protective grounding according to GE Speedtronic system specification.
- After replacement: verify ribbon‑cable link status, check MPU pulse signal quality, simulate all emergency‑trip input conditions, validate hardware trip‑action response before commissioning.
- Replacement note: For TMR triple‑redundant safety‑loop application, three‑set TREA hardware consistency must be verified; full emergency‑protection‑loop simulation test mandatory after swap.





-1-1-300x300.jpg)
Reviews