GE IS200TREGH1BDB TREG Emergency Trip Relay Terminal Board

IS200TREGH1BDB (TREG board) is safety‑critical emergency trip relay termination board for GE Speedtronic Mark VI gas‑steam turbine control system. It drives three emergency trip solenoid valves by redundant relay voting logic, implements 2‑out‑of‑3 hardware trip logic, eliminates single‑point‑failure risk for turbine emergency shutdown. It provides positive and negative DC power distribution for trip solenoids, and receives trip feedback contact signals for trip‑action confirmation. Conformal‑coated PCB is designed for harsh turbine‑hall environment. This board belongs to turbine safety‑related hardware; board failure may lead to false‑trip or fail‑to‑trip risk. Product status: Obsolete, spare‑part only supply available.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware & Electrical Specifications

  • Model:IS200TREGH1BDB
  • Part Number:IS200TREGH1BDB
  • Module Type:TREG Emergency Trip Relay Terminal Board
  • Mounting:Cabinet panel mounting inside turbine control cabinet
  • Power supply:System DC power for trip solenoid driving circuit
  • Relay quantity:12 relays on‑board; 9 relays configured for triple‑channel redundant voting mechanism
  • Trip solenoid interface:Drives 3 sets of emergency trip solenoid valves, supplies positive / negative DC excitation for solenoid coils
  • Hardware filter:4 ms hardware interlock filter for trip signal path
  • Trip response:Fast hardware‑level trip action for overspeed and emergency shutdown commands
  • Feedback input:Contact feedback inputs to confirm solenoid actual actuation status
  • Interface:Two barrier‑type screw terminal blocks for field solenoid and feedback wiring; multiple multi‑pin ribbon connectors for I/O controller interconnection
  • PCB treatment:H1‑series conformal coated for dust‑moisture‑corrosion resistance
  • On‑board protection:ESD protection, MOV surge suppression, built‑in energy‑storage capacitor groups for reliable trip action under momentary power fluctuationTriconex1 …
  • Compatibility note:Cannot run standalone; must match Mark VI I/O controller; full emergency‑trip solenoid simulation test mandatory after replacement.

Environmental Specifications

  • Operating temperature:0 ℃ ~ +60 ℃
  • Storage temperature:‑40 ℃ ~ +85 ℃
  • Relative humidity:5%‑95% non‑condensing
  • Installation location:Indoor turbine control cabinet
  • EMC compliance:IEC 61000‑6‑2
  • Certifications:CE

Mechanical Data

  • Weight:approx 0.77 kg
  • Dimension:178 mm × 330 mm × 50 mm
  • Handling note:ESD‑sensitive PCB; safety‑critical trip‑relay circuit, anti‑static wrist‑strap mandatory during handling
  • Recommended wire cross‑section:0.75‑2.5 mm² shielded twisted‑pair copper cable for solenoid and feedback‑contact wiring
  • Terminal tightening torque:0.6‑1.0 N·m

Main Functions

  1. Screw‑terminal field termination for three emergency trip solenoid valves and trip‑confirmation feedback contact signals.
  2. Redundant relay voting logic (9‑relay triple‑channel structure), supplies positive and negative DC power to trip solenoids to execute hardware emergency shutdown command, avoids single‑relay‑point failure causing safety‑loop malfunction.
  3. Receives feedback contact signals after solenoid actuation, confirms whether trip action is executed successfully.
  4. Built‑in energy‑storage capacitor groups ensure reliable trip output under short‑time power‑supply disturbance.
  5. On‑board hardware 4 ms filter suppresses field‑side transient interference from triggering mis‑trip.
  6. Supports online individual‑solenoid diagnostic test and offline overspeed‑condition simulation test via system software.
  7. On‑board self‑diagnosis: detect power‑supply abnormal, ribbon‑cable link failure and relay‑circuit fault, report fault status to turbine main controller.
  8. LED status indication:
    • Green LED:Board auxiliary power normal
    • Yellow LED:Ribbon‑cable link communication active
    • Red LED:Trip‑active / relay‑circuit fault / link‑failure alarm

Installation & Wiring Requirements

  1. Cut off rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
  2. Secure panel mounting firmly; ensure all multi‑pin ribbon‑cable connectors fully locked without loose contact.
  3. Field trip‑solenoid wiring strictly follow GE Speedtronic Mark VI wiring manual; safety‑related solenoid cables adopt shielded twisted‑pair, strictly separated from high‑power cables; connect shielding to dedicated ground terminal.
  4. Complete protective grounding according to GE Speedtronic system specification.
  5. After replacement: verify ribbon‑cable link status, execute solenoid on‑line test, simulate emergency trip condition, validate trip‑solenoid actuation and feedback‑signal response before commissioning.
  6. Replacement note: Verify relay‑voting‑logic function after swap; full emergency‑trip‑loop simulation test mandatory before unit put‑into‑service.

Reviews