Description
Hardware & Electrical Specifications
- Model:IS200TRLYH1BGF
- Part Number:IS200TRLYH1BGF
- Module Type:TRLY Relay Output Terminal Board
- Mounting:Cabinet panel mounting inside turbine control cabinet
- Logic power supply:24 VDC auxiliary power supplied by TRLY processor pack
- Relay quantity:12 channels Form‑C (SPDT) electromechanical relays
- Relay contact rating:5 A @250 VAC / 30 VDC resistive load; supports 125 VDC trip bus and 24 VDC alarm bus field voltage
- Isolation:1500 Vrms galvanic isolation between relay coil and contact side, suppress plant ground‑loop interference
- Response time:Relay actuation ≤10 ms
- Interface:Barrier‑type screw terminal blocks for field device wiring; multiple 50‑pin IDC ribbon‑cable connectors for TRLY processor interconnection; JA1 for simplex, JR1‑JS1‑JT1 for TMR redundant configuration
- PCB treatment:BGF enhanced conformal coated for dust‑moisture‑corrosion resistance
- On‑board protection:ESD protection, MOV surge suppression, snubber circuit for inductive load, relay coil current monitoring for fault diagnosis
- Compatibility note:Cannot run standalone; must match Mark VI / Mark VIe TRLY processor pack; full‑channel relay action simulation test mandatory after replacement.
Environmental Specifications
- Operating temperature:‑40 ℃ ~ +70 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Indoor turbine control cabinet
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Weight:approx 1.30 kg
- Dimension:178 mm × 330 mm × 45 mm
- Handling note:ESD‑sensitive PCB; electromechanical relay circuit, anti‑static wrist‑strap mandatory during handling
- Recommended wire cross‑section:0.75‑2.5 mm² shielded twisted‑pair copper cable for field solenoid and annunciator wiring
- Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Screw‑terminal field termination for external field devices: solenoid valves, alarm annunciator lamps, auxiliary interlock relays and partial protection loop equipment.
- Convert low‑voltage logic commands from TRLY processor into dry‑contact relay switching output, realize electrical isolation between control rack and plant field side.
- Relay coil current real‑time monitoring; compare actual excitation current with command value, detect relay coil open‑circuit or abnormal condition.
- Snubber absorption circuit suppresses reverse electromotive force of inductive loads, extend relay contact service life.
- On‑board self‑diagnosis: detect auxiliary power abnormal, ribbon‑cable link communication failure and relay‑circuit fault, upload fault alarm to turbine main controller.
- LED status indication:
- Green LED:Board auxiliary power normal
- Yellow LED:Ribbon‑cable link communication active
- Red LED:Relay‑channel fault / link‑failure alarm
Installation & Wiring Requirements
- Cut off rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Secure panel mounting firmly; ensure all 50‑pin IDC ribbon‑cable connectors fully locked without loose contact.
- Field device wiring strictly follow GE Speedtronic Mark VI wiring manual; adopt shielded twisted‑pair cables, strictly separated from high‑power cables; connect shielding to dedicated ground terminal.
- Complete protective grounding according to GE Speedtronic system specification.
- After replacement: verify ribbon‑cable link status, test every relay pull‑in and drop‑out action, validate field‑device response before commissioning.
- Replacement note: For TMR triple‑redundant system application, hardware consistency of related packs shall be verified; full‑channel relay‑output simulation test mandatory before unit put‑into‑service.