Description
Hardware & Electrical Specifications
- Model:IS200TVBAH2ABC
- Part Number:IS200TVBAH2ABC
- Module Type:TVBA Vibration Monitoring Terminal Board
- Mounting:Cabinet panel mounting inside turbine control cabinet
- Logic power supply:24‑28 VDC supplied by PVBA vibration‑monitor processor pack
- Vibration input channels:8 configurable analog input channels
- Supported sensor types:proximity probe (shaft displacement), accelerometer, velocity seismic sensor, 4‑20 mA loop‑powered vibration transmitter
- Input signal:±5 VDC for proximity probes; 4‑20 mA for transmitters, on‑board 250Ω precision sampling resistor
- Sensor excitation:‑24 VDC isolated excitation power for proximity probe pre‑amplifiers
- Signal bandwidth:DC‑1 kHz (‑3dB) anti‑aliasing hardware filter for vibration signal path
- Conversion resolution:16‑bit ADC analog‑to‑digital conversion
- Isolation:2500 Vrms galvanic isolation between field side and control rack side, suppress plant ground‑loop interference
- Interface:Removable barrier‑type screw terminal blocks for field vibration‑sensor wiring; multiple multi‑pin ribbon‑cable connectors for PVBA processor interconnection; buffered test output port for external vibration analyzer connection
- PCB treatment:ABC‑revision conformal coated for dust‑moisture‑corrosion resistance
- On‑board protection:ESD protection, MOV surge suppression, per‑channel over‑voltage / over‑current limiting, sensor open‑/short‑circuit fault detection circuit
- Compatibility note:Cannot run standalone; must match Mark VI / Mark VIe PVBA vibration‑monitor processor pack; full vibration‑loop simulation test mandatory after replacement.
Environmental Specifications
- Operating temperature:‑20 ℃ ~ +70 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Indoor turbine control cabinet
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Weight:approx 0.60 kg
- Dimension:233 mm × 160 mm × 28 mm
- Handling note:ESD‑sensitive PCB; high‑precision weak‑signal vibration‑conditioning circuit, anti‑static wrist‑strap mandatory during handling
- Recommended wire cross‑section:0.75‑2.5 mm² shielded twisted‑pair copper cable for proximity probe and vibration‑sensor wiring
- Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Removable screw‑terminal field termination for shaft proximity probes, bearing accelerometers, seismic velocity sensors and vibration 4‑20 mA transmitters.
- Provide isolated‑24 VDC excitation power for proximity probe pre‑amplifiers.
- Hardware filtering and conditioning for vibration analog signals, convert field weak vibration signals into standard analog values and transmit to PVBA processor pack.
- Buffered vibration test output port, supports external vibration instrument access for offline signal verification.
- Galvanic isolation between control rack and field‑side sensors, suppress turbine‑hall high‑EMI transient interference.
- On‑board channel self‑diagnosis: detect sensor open‑circuit / short‑circuit, excitation power abnormal, ribbon‑cable link failure; upload fault alarm to turbine main controller.
- LED status indication:
- Green LED:Board auxiliary power normal
- Yellow LED:Ribbon‑cable link communication active
- Red LED:Vibration‑channel fault / excitation‑power fault / link‑failure alarm
Installation & Wiring Requirements
- Cut off rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Secure panel mounting firmly; ensure all multi‑pin ribbon‑cable connectors fully locked without loose contact.
- Field vibration‑sensor wiring strictly follow GE Speedtronic Mark VI / Mark VIe wiring manual; vibration analog cables adopt high‑quality shielded twisted‑pair, strictly separated from high‑power cables; connect shielding to dedicated ground terminal.
- Complete protective grounding according to GE Speedtronic system specification.
- After replacement: verify ribbon‑cable link status, check each‑channel sensor excitation voltage, verify vibration measurement reading, simulate sensor fault condition before commissioning.
- Replacement note: For TMR triple‑redundant system application, hardware consistency of related PVBA packs shall be verified; full vibration‑monitor‑loop simulation test mandatory before unit put‑into‑service.