Description
Hardware & Electrical Specifications
- Model:IS200VAICH1DAB
- Part Number:IS200VAICH1DAB
- Module Type:VAIC VME‑Bus Analog Input‑Output Processor Board
- Mounting:6U VME rack backplane installation inside control cabinet
- Power supply:+5 VDC, ±15 VDC powered via VME backplane; 24 VDC field auxiliary power from terminal board
- Analog input:20 differential analog input channels; signal types: 4‑20 mA, 0‑20 mA, ±10 VDC jumper configurable
- Analog output:4‑channel configurable output; 4‑20 mA / 0‑200 mA selectable; max load resistance up to 800 Ω
- A‑D / D‑A conversion:16‑bit ADC resolution; 10 ms scan cycle (100 Hz) for turbine process loop
- Common‑mode rejection:AC CMR ≥60 dB@60 Hz; DC CMR ≥80 dB
- Interface:VME backplane bus interface; multi‑pin ribbon‑cable connectors for TBAIH1C / STAI terminal board interconnection
- PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance
- On‑board protection:ESD protection, MOV surge suppression, channel over‑voltage / over‑current limiting, open‑circuit detection for input/output channels, fault‑safety suicide relay for analog outputs
- Compatibility note:Cannot run standalone; must match Mark VI TBAIH1C or STAI terminal board; full analog‑loop simulation test mandatory after replacement.
Environmental Specifications
- Operating temperature:‑20 ℃ ~ +70 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Indoor turbine control cabinet
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Weight:approx 0.65 kg
- Dimension:260 mm × 180 mm × 25 mm
- Handling note:ESD‑sensitive PCB; high‑precision analog circuit, anti‑static wrist‑strap mandatory during handling
- Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Receive field analog signals transmitted from TBAIH1C / STAI terminal boards, including pressure transmitters, flow transmitters, temperature‑related analog transducers and other process 4‑20 mA / voltage signals.
- Complete analog‑to‑digital conversion, signal scaling and filtering, transmit digital process data to main controller via VME bus.
- Convert digital control commands from main rack into analog current output signals, drive field analog actuators or positioning devices.
- Built‑in suicide relay cuts off analog outputs when critical board fault occurs, improving system safety.
- Per‑channel self‑diagnosis: detect input over‑range, output over‑load, channel open‑circuit fault, ribbon‑cable link failure; upload fault alarm to turbine main controller.
- LED status indication:
- Green LED:Board power supply normal
- Yellow LED:VME bus and ribbon‑cable link communication active
- Red LED:Analog‑channel fault / link‑failure alarm
Installation & Wiring Requirements
- Cut off rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Insert board into designated VME slot, secure panel locking screws; ensure all multi‑pin ribbon‑cable connectors fully locked without loose contact.
- Field analog wiring strictly follow GE Speedtronic Mark VI wiring manual; analog signal cables adopt shielded twisted‑pair, strictly separated from high‑power cables; connect shielding to dedicated ground terminal.
- Complete protective grounding according to GE Speedtronic system specification.
- After replacement: verify VME rack power status, check each analog input reading, test every analog output channel performance before commissioning.
- Replacement note: For TMR triple‑redundant system application, hardware consistency of related packs shall be verified; full analog‑loop simulation test mandatory before unit put‑into‑service.