Description
Hardware & Electrical Specifications
- Model:IS200VCMIH2BEE
- Part Number:IS200VCMIH2BEE
- Module Type:VCMI VME‑Bus Master Communication Controller Board
- Mounting:6U single‑slot VME rack backplane installation inside control cabinet
- Power supply:+5 VDC, ±12 VDC powered via VME backplane
- Communication interface:3‑channel IONet fiber‑optic Ethernet ports for TMR configuration; VME backplane bus interface for internal rack communication
- Communication rate:10 Mbps IONet fiber‑optic network
- Fault‑tolerance:SIFT software‑implemented fault tolerance voting logic for TMR system data comparison
- Interface:Front‑panel fiber‑optic connectors; VME backplane connector for intra‑rack processor communication
- PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance
- On‑board protection:ESD protection, transient surge suppression, link‑status fault detection, communication channel error‑count monitoring circuit
- Compatibility note:Cannot run standalone; must match Mark VI VME‑based processor packs; full communication‑loop simulation test mandatory after replacement。
Environmental Specifications
- Operating temperature:0 ℃ ~ +70 ℃
- Storage temperature:‑40 ℃ ~ +85 ℃
- Relative humidity:5%‑95% non‑condensing
- Installation location:Indoor turbine control cabinet
- EMC compliance:IEC 61000‑6‑2
- Certifications:CE
Mechanical Data
- Weight:approx 0.75 kg
- Dimension:260 mm × 160 mm × 25 mm
- Handling note:ESD‑sensitive PCB; high‑speed fiber‑optic communication circuit, anti‑static wrist‑strap mandatory during handling
Main Functions
- Act as UDH master communication controller, realize real‑time IONet fiber‑optic data exchange between main control rack and remote I/O racks, processor packs and field terminal boards.
- Execute SIFT voting for TMR triple‑redundant system, complete data comparison, fault identification and faulty channel isolation.
- Transmit control commands from main CPU to distributed I/O modules; upload field measurement and protection status data back to main controller via VME bus.
- On‑board channel self‑diagnosis: detect fiber‑optic link break, communication frame error, VME‑bus abnormality; upload fault alarm to turbine main controller.
- LED status indication:
- Green LED:Board power supply normal
- Yellow LED:IONet fiber‑optic link communication active
- Red LED:Communication‑link fault / VME‑bus fault / module failure alarm
Installation & Wiring Requirements
- Cut off rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Insert board into designated VME slot, secure panel locking screws; properly connect fiber‑optic cables, avoid excessive bending radius of optical fiber.
- Fiber‑optic wiring strictly follow GE Speedtronic Mark VI wiring manual; keep optical fiber cables separated from high‑power interference cables.
- Complete protective grounding according to GE Speedtronic system specification.
- After replacement: verify VME rack power status, check each IONet link status, test data transmission between racks before commissioning.
- Replacement note: For TMR triple‑redundant system application, hardware consistency of related VCMI boards shall be verified; full communication‑loop simulation test mandatory before unit put‑into‑service.