Description
Hardware & Electrical Specifications
‑ Model:IS2020RKPSG3A ‑ Part Number:IS2020RKPSG3A ‑ Module Type:VME Rack Power Supply Module ‑ Mounting:Mounted on right side of Mark VI VME control rack via metal bracket ‑ Input:Nominal 125 VDC, operating range 90‑145 VDC, max input current 4.0 A full‑load ‑ Total output power:400 W ‑ Output rails:+5 VDC, ±12 VDC, ±15 VDC, +28 VDC, specialized 335 VDC for flame detector circuits; multiple remote +28 V PSA auxiliary outputs ‑ Front‑panel control:Locking toggle switch for power ON/OFF and fault reset ‑ Front‑panel indicators:Green(Power OK), Yellow(Input status), Red(Fault alarm) ‑ Connector:PSA / PSB harness to VME backplane; PS125 input, PS335, PS28, PSSTAT status signal connectors at bottom ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:Over‑voltage, over‑current, short‑circuit, thermal shutdown protection, built‑in power‑loop self‑diagnosis, status‑ID signal output to rack monitoring ‑ Compatibility note:Cannot run standalone; must match Mark VI VME rack backplane and system distribution hardware; full power‑loop test mandatory after replacement.
Environmental Specifications
‑ Operating temperature:0 ℃ ~ +60 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor turbine control cabinet ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous‑location certification
Mechanical Data
‑ Weight:approx 7.1 kg ‑ Dimension:330 × 180 × 385 mm ‑ Handling note:ESD‑sensitive power module, contains high‑voltage 335 VDC circuit; anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Accepts 125 VDC cabinet system input, converts and provides multi‑channel stabilized DC power for VME rack controller boards, signal I/O cards.
- Provides dedicated 335 VDC power supply for flame detector detection circuit of gas turbine.
- Supplies multiple remote +28 V auxiliary power outputs for external field peripherals.
- Real‑time monitors input voltage, each output rail status, over‑temperature and fault conditions; outputs status‑ID diagnostic signal to rack monitoring system.
- Built‑in complete hardware protection: over‑voltage, over‑current, short‑circuit and thermal protection to avoid secondary damage to rack boards.
- LED status indication: ‑ Green LED:Module power supply normal ‑ Yellow LED:Input power presence indicator ‑ Red LED:Module fault / protection shutdown alarm
Installation & Wiring Requirements
- Completely cut off 125 VDC input power before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling power module.
- Securely install module on right‑side bracket of VME rack, fasten mounting screws; correctly connect PSA/PSB backplane harness and bottom input/output cables.
- Wiring strictly follow GE Mark VI hardware manual; separate high‑power power cables from small‑signal control cables, connect shielding to dedicated protective ground terminal.
- Complete protective grounding according to GE system specification.
- After replacement: step‑by‑step power‑on, verify all output rail voltage values, check front‑panel LED status, perform fault simulation test.
- Replacement note: For TMR triple‑redundant rack application, verify hardware consistency; full power‑supply‑loop simulation test mandatory before unit put‑into‑service.