Description
Hardware & Electrical Specifications
‑ Model:IS215VPROH1BD ‑ Part Number:IS215VPROH1BD ‑ Module Type:VPRO Emergency Turbine Protection Module ‑ Mounting:6U single‑slot VME rack installation ‑ Power supply:+5 VDC, ±12 VDC powered via VME backplane; trip circuit power 125 VDC (70‑145 VDC) ‑ On‑board processor:Dedicated safety processor for speed measurement and protection logic ‑ Signal interfaces: • MPU magnetic pickup speed sensor input channels for turbine speed acquisition • Dry‑contact discrete trip input channels • Trip drive output interface connected to TREG terminal board for trip solenoid control • VME bus interface for status data upload to main controller ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:ESD protection, MOV surge suppression, hardware watchdog self‑monitor circuit, signal channel isolation, built‑in self‑diagnosis for overspeed detection circuit ‑ Compatibility note:Cannot run standalone; must match Mark VI VME rack, UCV main controller and TREG terminal board; full protection‑loop simulation test mandatory after replacement。
Environmental Specifications
‑ Operating temperature:‑25 ℃ ~ +70 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor turbine control cabinet ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE
Mechanical Data
‑ Weight:approx 1.5 kg ‑ Dimension:280 mm × 160 mm × 25 mm (6U VME standard form‑factor) ‑ Handling note:ESD‑sensitive PCB; safety protection circuit, anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Independent hardware overspeed protection: acquires turbine speed signal from MPU sensors, executes hardware overspeed trip logic independent of main CPU software.
- Process external emergency trip dry‑contact signals, output trip drive signal to TREG board to actuate trip solenoid for turbine emergency shutdown.
- Real‑time self‑diagnosis for speed measurement channel, trip circuit and module hardware; upload fault status and protection action record to main controller via VME bus.
- LED status indication: ‑ Green LED:Board power supply normal / RUN status ‑ Yellow LED:Speed signal / input channel activity indicator ‑ Red LED:Module FAIL / protection trip fault alarm
Installation & Wiring Requirements
- Cut off rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Insert board into designated VME slot, secure panel locking screws; ensure VME backplane contact is reliable.
- MPU speed sensor, trip contact and TREG wiring strictly follow GE Speedtronic Mark VI wiring manual; signal cables shall be separated from high‑power cables; connect shielding to dedicated ground terminal.
- Complete protective grounding according to GE system specification.
- After replacement: verify VME rack power‑on status, check MPU speed reading, perform overspeed simulation test and trip loop commissioning test.
-
Replacement note: For TMR triple‑redundant system application, hardware consistency and firmware‑version matching of redundant VPRO modules shall be verified; full protection‑loop simulation test mandatory before unit put‑into‑service.