Description
Hardware & Electrical Specifications
‑ Model:IS220PAICH1A ‑ Part Number:IS220PAICH1A ‑ Module Type:PAI Analog Input Module ‑ Mounting:Installed in Mark VIe I/O pack rack ‑ Power supply:24 VDC field power supplied via I/O pack backplane ‑ Input channels:Multi‑channel analog input, supports 4‑20 mA current signal and ±10 V voltage signal ‑ Communication interfaces: • IONet interface for communication with VCMI / controller • Backplane interface inside I/O pack ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:ESD protection, MOV surge suppression, channel signal isolation, module self‑diagnosis circuit ‑ Compatibility note:Cannot run standalone; must match Mark VIe I/O pack rack and corresponding controller hardware; full signal‑loop simulation test mandatory after replacement.
Environmental Specifications
‑ Operating temperature:‑40 ℃ ~ +70 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor turbine control cabinet ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE
Mechanical Data
‑ Weight:approx 0.35 kg ‑ Dimension:Standard Mark VIe I/O pack module form‑factor ‑ Handling note:ESD‑sensitive PCB; analog signal acquisition circuit, anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Acquire field analog signals including 4‑20 mA and ±10 V from transmitters and process instruments.
- Perform analog‑to‑digital conversion, signal filtering and scaling for process variables.
- Transmit converted digital process data to main controller through IONet field bus.
- Execute continuous self‑diagnosis for each input channel, detect open‑circuit, over‑range and module hardware faults, and report fault status.
- LED status indication: ‑ Green LED:Module power supply normal / RUN status ‑ Yellow LED:Channel signal activity indicator ‑ Red LED:Module FAIL / channel fault alarm
Installation & Wiring Requirements
- Cut off I/O pack rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Insert module into designated slot of I/O pack rack, lock module latch to ensure reliable backplane contact.
- Field analog signal wiring strictly follow GE Speedtronic Mark VIe wiring manual; signal cables shall be separated from high‑power cables; connect shielding to dedicated ground terminal.
- Complete protective grounding according to GE system specification.
- After replacement: verify I/O pack power‑on status, check each channel signal reading, perform analog‑loop commissioning test.
- Replacement note: For TMR triple‑redundant system application, hardware consistency and firmware‑version matching shall be verified; full signal‑loop simulation test mandatory before unit put‑into‑service.






-1-1-300x300.jpg)