GE IS220PDIAH1B PDIA Discrete Contact Input I/O Pack

IS220PDIAH1B (PDIAH1B) is 24‑channel discrete contact input I/O pack for GE Speedtronic Mark VIe / Mark VIeS turbine‑generator control system, hardware revision B upgraded version of IS220PDIAH1AMoore Auto…. It acquires dry‑contact and 24 VDC digital status signals from field switches, limit switches, interlock relays and push‑buttons, supports SOE sequence‑of‑event time‑stamping function. Supports simplex, duplex and TMR triple‑modular‑redundant I/O configuration. Product status: Obsolete, spare‑part only supply available。

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware & Electrical Specifications

‑ Model:IS220PDIAH1B ‑ Part Number:IS220PDIAH1B ‑ Module Type:PDIA Discrete Contact Input I/O Pack ‑ Mounting:Installed in Mark VIe I/O pack rack ‑ Power supply:24 VDC backplane power, max 28.6 VDC; contact input max 32 VDC ‑ Input channels:24 optically‑isolated discrete contact input channels, supports dry‑contact / 24 VDC sensing, programmable input filter 1‑20 ms ‑ Communication interfaces:  • Dual redundant 100 Mbps RJ45 IONet Ethernet ports for controller communication  • DC‑37‑pin connector for connection to matching discrete input terminal boards ‑ Compatible terminal boards:IS200STCIH1A, IS200STCIH2A, IS200STCIH8A, IS200TBCIH2C etc ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:ESD protection, MOV surge suppression, optical channel isolation (1500 V), built‑in self‑diagnosis circuit for channel and hardware fault detection ‑ Compatibility note:Cannot run standalone; must match Mark VIe I/O pack rack and corresponding controller hardware; full signal‑loop simulation test mandatory after replacement.

Environmental Specifications

‑ Operating temperature:‑40 ℃ ~ +70 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor turbine control cabinet ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous location certificationMOORE AUTO…

Mechanical Data

‑ Weight:approx 0.42 kg ‑ Dimension:Standard Mark VIe I/O pack module form‑factor ‑ Handling note:ESD‑sensitive PCB; discrete signal acquisition circuit, anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m

Main Functions

  1. Collect field discrete on‑off status signals from limit switches, interlock contacts, push‑buttons and relay dry contacts.
  2. Perform signal filtering, optical isolation and digitization; provide high‑precision SOE time‑stamping for contact state change events.
  3. Transmit digital status data and SOE event records to main controller via redundant IONet bus.
  4. Continuous self‑diagnosis for each input channel, detect abnormal input and module hardware faults, upload fault alarm status.
  5. LED status indication:   ‑ Green LED:Module power supply normal / RUN status   ‑ Yellow LED:Channel signal / IONet link activity indicator   ‑ Red LED:Module FAIL / channel fault alarm

Installation & Wiring Requirements

  1. Cut off I/O pack rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
  2. Insert module into designated slot of I/O pack rack, lock module latch to ensure reliable backplane contact.
  3. Field discrete signal wiring strictly follow GE Speedtronic Mark VIe wiring manual; signal cables shall be separated from high‑power cables; connect shielding to dedicated ground terminal.
  4. Complete protective grounding according to GE system specification.
  5. After replacement: verify I/O pack power‑on status, check each channel status reading, perform discrete‑loop commissioning and SOE function test.
  6. Replacement note: For TMR triple‑redundant system application, hardware consistency and firmware‑version matching shall be verified; full signal‑loop simulation test mandatory before unit put‑into‑service.