Description
Hardware & Electrical Specifications
‑ Model:IS220PDIAH1BE ‑ Part Number:IS220PDIAH1BE ‑ Module Type:PDIA Wide‑Temperature Discrete Contact Input I/O Pack ‑ Mounting:Installed in Mark VIe I/O pack rack ‑ Power supply:24 VDC backplane power, max 28.6 VDC; contact input max 32 VDC ‑ Input channels:24 optically‑isolated discrete contact input channels, supports dry‑contact / 24 VDC sensing, programmable input filter 1‑20 ms ‑ Communication interfaces: • Dual redundant 100 Mbps RJ45 IONet Ethernet ports for controller communication • DC‑37‑pin connector for connection to matching discrete input terminal boards ‑ Compatible terminal boards:IS200STCIH1A, IS200STCIH2A, IS200STCIH8A, IS200TBCIH2C, IS400TBCIH2C etc ‑ PCB treatment:Enhanced conformal coated for dust‑moisture‑corrosion resistance, wide‑temperature grade ‑ On‑board protection:ESD protection, MOV surge suppression, optical channel isolation (1500 V), built‑in self‑diagnosis circuit for channel and hardware fault detection ‑ Compatibility note:Cannot run standalone; must match Mark VIe I/O pack rack and corresponding controller hardware; full signal‑loop simulation test mandatory after replacement.
Environmental Specifications
‑ Operating temperature:‑30 ℃ ~ +65 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor turbine control cabinet, suitable for relatively harsh cabinet temperature condition ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous location certification
Mechanical Data
‑ Weight:approx 0.42 kg ‑ Dimension:Standard Mark VIe I/O pack module form‑factor ‑ Handling note:ESD‑sensitive PCB; discrete signal acquisition circuit, anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Collect field discrete on‑off status signals from limit switches, interlock contacts, push‑buttons and relay dry contacts.
- Perform signal filtering, optical isolation and digitization; provide high‑precision SOE time‑stamping for contact state change events.
- Transmit digital status data and SOE event records to main controller via redundant IONet bus.
- Execute continuous self‑diagnosis for each input channel, detect abnormal input and module hardware faults, and report fault alarm status.
- LED status indication: ‑ Green LED:Module power supply normal / RUN status ‑ Yellow LED:Channel signal / IONet link activity indicator ‑ Red LED:Module FAIL / channel fault alarm
Installation & Wiring Requirements
- Cut off I/O pack rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Insert module into designated slot of I/O pack rack, lock module latch to ensure reliable backplane contact.
- Field discrete signal wiring strictly follow GE Speedtronic Mark VIe wiring manual; signal cables shall be separated from high‑power cables; connect shielding to dedicated ground terminal.
- Complete protective grounding according to GE system specification.
- After replacement: verify I/O pack power‑on status, check each channel status reading, perform discrete‑loop commissioning and SOE function test.
- Replacement note: For TMR triple‑redundant system application, hardware consistency and firmware‑version matching shall be verified; full signal‑loop simulation test mandatory before unit put‑into‑service.






-300x300.jpg)