Description
Hardware & Electrical Specifications
‑ Model:IS220PDOAH1A ‑ Part Number:IS220PDOAH1A ‑ Module Type:PDOA Discrete Relay Output I/O Pack ‑ Mounting:Installed in Mark VIe I/O pack rack ‑ Power supply:24 VDC backplane power, operating range 22.8‑28.6 VDC, typical power consumption 8.5 W ‑ Output channels:12‑channel relay drive outputs, works with external relays on terminal boards; typical response time approx 6 ms from Ethernet command to contact actuation ‑ Communication interfaces: • Dual redundant 100 Mbps RJ45 IONet Ethernet ports for controller communication • DC‑37‑pin connector for connection to discrete output terminal boards ‑ Compatible terminal boards:TRLYH1B, TRLYH1C, SRLY series terminal boards ‑ PCB treatment:Conformal coated for dust‑moisture‑corrosion resistance ‑ On‑board protection:ESD protection, MOV surge suppression, optical isolation 1500 V between field and logic side, built‑in self‑diagnosis for drive circuit, open‑circuit and hardware fault detection ‑ Compatibility note:Cannot run standalone; must match Mark VIe I/O pack rack, main controller and corresponding TRLY/SRLY terminal boards; full signal‑loop simulation test mandatory after replacement.
Environmental Specifications
‑ Operating temperature:‑30 ℃ ~ +65 ℃ ‑ Storage temperature:‑40 ℃ ~ +85 ℃ ‑ Relative humidity:5%‑95% non‑condensing ‑ Installation location:Indoor turbine control cabinet ‑ EMC compliance:IEC 61000‑6‑2 ‑ Certifications:CE, UL Class I Div 2 hazardous location certification
Mechanical Data
‑ Weight:approx 0.5 kg ‑ Dimension:Standard Mark VIe I/O pack module form‑factor ‑ Handling note:ESD‑sensitive PCB; relay drive circuit, anti‑static wrist‑strap mandatory during handling ‑ Terminal tightening torque:0.6‑1.0 N·m
Main Functions
- Receive discrete on‑off control commands from Mark VIe main controller via redundant IONet bus.
- Generate drive signals for external relays mounted on matched terminal boards to control solenoid valves, contactors, trip coils, indicator lamps and auxiliary devices.
- Read relay‑contact feedback status from terminal board and upload real‑time output state to the controller.
- Continuous self‑diagnosis for each output drive channel, detect open‑circuit, abnormal load and module hardware faults, report fault alarm status.
- LED status indication: ‑ Green LED:Module power supply normal / PWR status ‑ Yellow LED:LINK / TxRx IONet communication activity indicator ‑ Red LED:ATTN / module FAIL fault alarm
Installation & Wiring Requirements
- Cut off I/O pack rack power supply before replacement. Hot‑swap is forbidden. Strict anti‑static protection when handling PCB board.
- Insert module into designated slot of I/O pack rack, lock module latch to ensure reliable backplane contact.
- Field discrete output wiring strictly follow GE Speedtronic Mark VIe wiring manual; signal cables shall be separated from high‑power cables; connect shielding to dedicated ground terminal.
- Complete protective grounding according to GE system specification.
- After replacement: verify I/O pack power‑on status, perform each channel output test and output‑loop commissioning test.
- Replacement note: For TMR triple‑redundant system application, hardware consistency and firmware‑version matching shall be verified; full signal‑loop simulation test mandatory before unit put‑into‑service.







Reviews