GE SLN080 IC086SLN080-A PACSystems Industrial Unmanaged Ethernet Switch

IC086SLN080‑A (SLN080) is a DIN‑rail mounted industrial unmanaged fast Ethernet switch, designed for harsh industrial sites such as power generation and oil & gas, compatible with PACSystems RX7i/RX3i control systems. Suffix ‑A denotes hardware revision A.
It provides eight 10/100Base‑TX copper RJ45 ports, supports fast ring recovery with recovery time less than 10 ms, dual redundant power inputs and fault alarm relay output, and integrates read‑only web diagnostic pages. It is plug‑and‑play without complex configuration, suitable for industrial Ethernet data exchange among field devices, PLCs and HMIs. The product is obsolete and available only in the spare‑parts market. DIN‑rail mounting; the unit itself is non‑hot‑swappable. Reference manual: GFK‑2487.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

Hardware & Electrical Specifications

‑ Model: IC086SLN080‑A ‑ Part Number: IC086SLN080‑A ‑ Type: DIN‑rail unmanaged industrial Ethernet switch ‑ Port configuration: 8 × RJ45 10/100Base‑T(X), auto‑negotiation, Auto‑MDI‑X ‑ Ethernet Standards: IEEE 802.3 (10Base‑T), IEEE 802.3u (100Base‑TX), IEEE 802.3x flow‑control ‑ Redundancy feature: Fast network recovery < 10 ms; dual redundant power input; fault‑alarm relay output (dry‑contact) ‑ Diagnostic access: Built‑in web‑based read‑only status monitoring page, no port configuration capability ‑ Power supply: 12‑24 VDC dual‑redundant input; max power consumption 6 W ‑ Isolation: 1500 VAC isolation between Ethernet ports and power interface ‑ Mounting: Standard 35 mm DIN‑rail mounting ‑ Diagnostics: Power‑on self‑test, port link‑activity monitoring, power‑fail alarm, network ring‑fault relay output ‑ PCB treatment: Standard industrial coated hardware ‑ Compatibility note: Compatible with GE PACSystems RX3i / RX7i, third‑party PLCs, HMIs and industrial devices. After replacement, verify power‑supply redundancy, link status of all ports, relay‑alarm function and web diagnostic page accessibility.

Environmental Specifications

‑ Operating temperature: ‑40 ℃ ~ +70 ℃ wide industrial temperature range ‑ Storage temperature: −40 ℃ ~ +85 ℃ ‑ Relative humidity: 5‑95 %RH non‑condensing ‑ Vibration: IEC 60068‑2‑6; Shock: IEC 60068‑2‑27 ‑ Installation location: Inside control cabinet, Pollution Degree 2, IP30 housing ‑ EMC compliance: IEC 61000‑6‑2, IEC 61000‑6‑4 ‑ Certifications: CE, UL Class I Div 2 hazardous‑location certification, EN 61010‑1

Mechanical Data

‑ Weight: approx 0.40 kg ‑ Dimension(W×H×D): 130.5 mm × 45 mm × 114.3 mm ‑ Mounting: 35 mm DIN‑rail snap‑on installation

Main Functions

  1. Plug‑and‑play industrial Layer‑2 switching for connecting PLCs, HMIs, I/O devices and field instruments inside control cabinets.
  2. Dual‑redundant DC power input avoids single power‑source failure; fault‑alarm dry‑contact relay reports power loss or hardware fault to external alarm systems.
  3. Fast network recovery (< 10 ms) supports ring topology for high‑availability industrial networks to minimize control‑network outage risk. Read‑only web page provides runtime status viewing.
  4. Front‑panel LED indicators:  ‑ PWR1 / PWR2: Redundant power‑supply status  ‑ FAULT: Power loss, hardware fault or ring‑network failure  ‑ P1‑P8 LINK/ACT: Individual port link and data‑activity status

Installation & Wiring Requirements

  1. Disconnect DC power before installation or replacement. Not hot‑swappable. Apply ESD protection during handling.
  2. Snap the unit onto standard 35 mm DIN‑rail. Wire dual 12‑24 VDC redundant power supply to terminal blocks; wire fault‑alarm relay dry‑contact to external alarm circuit. Connect shielded CAT5e Ethernet cables to RJ45 ports according to network topology.
  3. Cabling shall comply with manual GFK‑2487; maintain proper cable bending radius. Protective earth connection for cabinet is mandatory.
  4. After replacement: Restore DC power and check front‑panel LED status. Verify link status of each Ethernet port, test dual‑power fail‑over and fault‑relay alarm function. Access built‑in web diagnostic page to confirm module health status.
  5. Replacement note: This is an unmanaged switch; VLAN / QoS cannot be configured. Full‑system commissioning test is mandatory before putting into service.

Reviews

There are no reviews yet.

Be the first to review “GE SLN080 IC086SLN080-A PACSystems Industrial Unmanaged Ethernet Switch”

Your email address will not be published. Required fields are marked *