ICS T8110C TMR Main Processor Module

The T8110C is a TMR triple‑modular‑redundancy main processor module of ICS Triplex Trusted series. Compliant with IEC61508 SIL3 safety standard, it adopts 2‑out‑of‑3 voting architecture and supports hot‑swap. This module executes safety interlock logic, manages local and expansion I/O racks, features hardware self‑diagnosis and timestamped fault logging. It supports active‑standby dual‑CPU redundant configuration, widely used in ESD emergency shutdown and fire‑gas safety control systems for petrochemical, power and oil‑gas industries.
Email:2306444920@qq.com
Phone:+86 17759635229

Description

1. Basic Information

表格
Item Content
Model T8110C
Series Trusted TMR Triple Redundant Safety Control System
Product Type Main Processor CPU Module
Safety Certification IEC61508 SIL3, 2oo3 2‑out‑of‑3 voting architecture
Installation Rack slot mounting (Trusted chassis), hot‑swap supported
Manufacturer Former ICS‑Triplex, now Rockwell Automation

2. Hardware Specifications

  1. Power Supply
  • Backplane power: 20‑32VDC (nominal 24VDC), dual redundant backplane power supply; total power consumption approx. 75‑80W
  1. Processor & Memory
  • 32‑bit TMR triple‑processor parallel voting;
  • DRAM: 16 MB; EPROM: 512 KB; Flash: 2 MB; 128 KB battery‑backed NVRAM for program and fault log retention during power loss.
  1. Communication Interfaces
  • Backplane TMR bus for local / expansion I/O rack connection;
  • Ethernet, RS232 debug port, RS485; supports Modbus TCP and Trusted proprietary protocol for connection to engineering workstations and HMI host systems.
  1. Environmental Conditions
  • Operating temperature: ‑40℃ ~ +70℃;
  • Ingress protection IP20 (inside rack); for industrial cabinet installation.

3. Key Functions

  1. TMR Triple‑Modular Redundancy Voting: Three CPU channels run synchronously with 2‑out‑of‑3 voting. The system continues disturbance‑free operation if one processor channel fails. On‑line module replacement without shutdown.
  2. Comprehensive Hardware Self‑diagnosis: Real‑time monitoring of CPU, memory, communication and backplane. Time‑stamped fault logging. Front‑panel LED status indicators (Health, Run, Fault).
  3. Safety Logic Execution: Runs IEC61131‑3 programs (Ladder Diagram, Structured Text) for ESD emergency shutdown, fire‑gas protection and interlock logic.
  4. I/O Rack Management: Controls local racks and remote expansion I/O racks, drives T8xxx series I/O cards.
  5. Redundancy Configuration: Supports dual‑processor (active‑standby T8110C) hot‑standby mode for higher availability.

4. Typical Applications

‑ ESD emergency shutdown systems for petrochemical & chemical plants

‑ Safety interlocks for steam turbines and boilers in power plants

‑ Fire & Gas (F&G) safety systems for offshore oil‑gas platforms

‑ Other critical safety control applications requiring SIL3 rating

5. Important Notes

  1. Firmware version must match firmware of all system I/O modules. Mismatched firmware triggers voting faults and may cause system shutdown. Always check firmware build number when replacing spares.
  2. Spare part distinction: T8110B is legacy version; T8110C is upgraded variant. Do not mix installation without validation.
  3. NVRAM relies on the on‑board battery. Data retention will fail as battery ages; battery replacement on periodic basis is required.
  4. This module works only with dedicated Trusted chassis; incompatible with standard PLC racks.

Reviews

There are no reviews yet.

Be the first to review “ICS T8110C TMR Main Processor Module”

Your email address will not be published. Required fields are marked *