ICS T8310 TMR Expander Processor Module

The T8310 is a TMR triple‑modular‑redundancy expander processor module of ICS Triplex Trusted series. It meets IEC61508 SIL3 safety requirement with 2‑out‑of‑3 voting architecture and hot‑swap capability. Mounted in the left‑side processor slot of Trusted expander chassis, it executes local TMR processing and diagnostics for expander‑chassis I/O modules. It establishes high‑speed safe data exchange with main‑chassis T8161B by TC‑301 cable and T8312 adapter, and implements fault containment. It is widely used for multi‑rack expansion of large‑scale SIS safety instrumented systems for petrochemical, oil‑gas and power industries.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

1. Basic Information

表格
Item Content
Model T8310
Series Trusted T8000 TMR Triple‑Redundant Safety Control System
Product Type TMR Expander Processor Module
Safety Certification IEC61508 SIL3, TÜV certified, 2‑out‑of‑3 voting architecture
Installation Dual‑slot processor slot on left side of expander chassis, hot‑swap supportedNEX Instru…
Manufacturer ICS‑Triplex (Rockwell Automation)

2. Hardware Specifications

  1. Electrical Specifications

    ‑Backplane power supply:20‑32VDC powered by chassis backplane; typical power consumption approx.40W

    ‑Architecture:Three independent 32‑bit RISC processors, TMR triple‑modular redundancy with HIFT hardware fault tolerance; 2MB RAM, 8MB Flash ROM

    ‑High‑speed link rate: 250 Mbps, communication via TC‑301 hot‑link cable and T8312 adapter unitNEX Instru….

  2. Front‑panel & Indicators

    ‑Multi‑group front‑panel LEDs: Module OK, Fault, Link status, Voting status;

    ‑Hot‑swap handle for on‑line replacement without interrupting other expander chassis.

  3. Environmental Conditions

    ‑Operating temperature:0℃ ~ +60℃; Storage temperature:‑25℃ ~ +85℃

    ‑Relative humidity:5‑95% non‑condensing; IP20 (inside cabinet); EMC anti‑interference, shock‑vibration resistant for industrial environment.

3. Key Functions

  1. Local TMR processing for expander chassis: All I/O modules inside expander chassis complete local three‑channel data acquisition, voting and fault diagnostics by T8310, reducing computing load of main‑chassis T8110C / T8111C main processors.
  2. High‑speed safe bridging to main chassis: Interconnect main‑chassis T8161B expander‑interface via T8312 adapter and TC‑301 cable. Deterministic low‑latency safe data transmission is realized. I/O points are transparent to main CPU without program modification.
  3. Fault tolerance and fault containment: HIFT hardware fault‑tolerant technology. Single‑channel faults are isolated automatically. Supports automatic / manual repair strategy and hot‑standby module. Faults from expander side cannot propagate to main‑chassis core control areaNEX Instru….
  4. Comprehensive self‑diagnosis: Real‑time monitoring of three‑channel status, backplane, high‑speed link and I/O subsystem. Timestamped fault messages uploaded to system software; front‑panel LEDs support fast on‑site troubleshooting.
  5. Hot‑swap maintenance: Faulty module can be replaced online without shutdown of whole SIS system.

4. Typical Applications

‑Remote I/O expander chassis for Trusted system; T8310 is mandatory for each expander chassis

‑Large‑scale SIS projects with distributed cabinet layout for petrochemical & chemical ESD emergency shutdown and F&G fire‑gas systems

‑Safety instrumented systems on offshore oil‑gas platforms and power plants with multiple remote I/O expander cabinets

5. Important Notes

  1. T8310 is only for expander chassis, cannot be fitted into T8100 main chassis, and cannot replace T8110C / T8111C main processor.
  2. Matching accessories: TC‑301 hot‑link cable, T8312 expander‑interface adapter unit; main chassis shall be equipped with T8161B expander‑interface module.
  3. Firmware version must strictly match main‑chassis T8110C/T8111C and T8161B. Mismatched firmware will cause expander‑chassis communication failure. Verify firmware build‑number for spare‑part replacement.
  4. T8310 must be installed on left‑hand processor slot of expander chassis, otherwise expander‑chassis I/O modules cannot work normally.
  5. Only compatible with Trusted T8000‑series expander chassis, not applicable for other generic PLC racks.