ICS T8402 (ICS T8402 60‑Channel 24VDC Digital Input Module

The T8402 is 60‑channel 24VDC digital input module for ICS Triplex Trusted T8000 SIS platform. Internal 1oo2D fault‑tolerant voting architecture delivers SIL3 capability with hardware‑timestamped SOE at 1 ms resolution and hot‑swap maintainability. It requires T8802 FTA for field wiring termination for high‑density discrete safety‑signal acquisition. Being end‑of‑life, it is only used for spare‑part maintenance of legacy ESD/F&G installations across petrochemical, power and offshore oil‑gas industries.

Email:2735429704@qq.com
Phone:+86 19316626421

Description

1. Basic Information

Item Content
Model T8402
Series Trusted T8000 TMR Triple‑Redundant Safety Control System
Product Type 60‑Channel 24VDC Digital Input Module
Safety Certification IEC61508 SIL3, TÜV approved, 3‑2‑0 fault‑tolerant architecture
Installation Slot‑mount inside T8100 main chassis or T8300 expander chassis, hot‑swap supported
Matching FTA T8802 (60‑channel field termination assembly)Rockwell A…
Manufacturer ICS‑Triplex (Rockwell Automation)
Lifecycle End‑of‑life, no brand‑new original production

2. Hardware Specifications

  1. Electrical & Channel

    ‑Channel count: 60 channels of 24 VDC digital input, internal dual‑path 1oo2D voting per channel

    ‑Field input voltage:24 VDC, configurable logic threshold; typical per‑channel input current 6 mA

    ‑Backplane power:20‑32 VDC from chassis backplane; typical power consumption 3 W

    ‑Sampling:σ‑δ ADC sampling circuit, dual voltage measurement per channel. Individual channel‑wise line‑monitoring for wire‑break and short‑circuit detection, configurable by software

    ‑SOE function:On‑board hardware SOE, 1 ms time‑stamp resolution, event triggered upon status change

    ‑Isolation:Galvanic isolation between field side and system side, surge withstand up to 2 kV.

  2. Front‑panel & Interface

    ‑Front‑panel LEDs:Module OK, Fault, backplane bus status.

    ‑Rear‑side 96‑way connector connects to T8802 FTA; Smart‑slot supports hot‑module‑replacement without disconnecting field wiring.

  3. Environmental Conditions

    ‑Operating temperature:0℃ ~ +60℃; Storage temperature:‑40℃ ~ +85℃

    ‑Relative humidity:5‑95 % non‑condensing; IP20 for cabinet installation; ATEX Zone 2 certified; industrial shock‑vibration resistance.

3. Key Functions

  1. 1oo2D dual‑path voting acquisition:Each field signal goes through two independent acquisition circuits inside module. Local 1oo2D voting is executed; faulty channel is isolated automatically without impact to other channels.
  2. Per‑channel line diagnostics:When line‑monitor is enabled, wire‑break and short‑circuit can be detected; timestamped fault messages uploaded to system software.
  3. Hardware‑based SOE:Event time‑stamp processed locally on module with 1 ms resolution for safety post‑event analysis, without loading main controller CPU.
  4. Hot‑swap maintenance:Module can be replaced online; field wiring on FTA side remains connected; other I/O channels keep running normally.
  5. Compatible with TMR system bus:Can be installed either in main chassis or T8300 remote expander chassis; I/O points are fully transparent to main processor.

4. Typical Applications

‑Petrochemical & chemical ESD emergency shutdown, F&G fire‑gas systems for large‑volume digital‑signal acquisition (pressure switches, level switches, flame detectors, ESD push‑buttons etc).

‑Safety‑instrumented systems for power‑plant and offshore oil‑gas platforms with high‑density discrete signals.

‑Legacy‑system spare‑part replacement; new‑project alternative model:T8403 (40‑channel DI).

5. Important Notes

  1. T8402 must pair with T8802 FTA, cannot connect field cables directly. T8802 is DIN‑rail mounted, each channel equipped with field‑loop fuse protectionRockwell A….
  2. It can be fitted into main chassis or T8300 expander chassis; T8310 expander‑processor must be present if used inside expander chassis.
  3. Firmware build‑version must match whole system firmware, verify build‑number before spare‑part replacement.
  4. Original manufacturing stopped(EOL); only second‑hand / refurbished / surplus stock available. For new projects select T8403 instead.
  5. Line‑monitor function requires corresponding resistors configured on FTA and software enable per‑channel; without enable only on‑off status is read without wire‑break diagnosis.

Reviews

There are no reviews yet.

Be the first to review “ICS T8402 (ICS T8402 60‑Channel 24VDC Digital Input Module”