Description
1. Basic Information
表格
| Item | Content |
|---|---|
| Model | T8800 (Standard version only, no conformal coated variant) |
| Series | Trusted T8000 TMR Triple Modular Redundant Safety Instrumented System |
| Product Type | 40‑Channel 24VDC Digital Input Field Termination Assembly (FTA) |
| Matched I/O Module | T8403 / T8403C 40‑Channel 24VDC Digital Input Module |
| Interface Connector | Dual 96‑Way SmartSlot socket for connection to T8403 I/O module |
| Mounting | TS32 / TS35 standard DIN‑rail mounting, horizontal / vertical installation allowed |
| Manufacturer | ICS‑Triplex (Rockwell Automation) |
| Warranty | 12‑month standard factory warranty |
| BOM Part‑Name | T8800, FTA, 40‑Channel 24VDC Digital Input |
| Weight | Approx. 0.9 kg |
2. Electrical Specifications
- Channel quantity: 40 digital input channels, 2‑wire field signal wiring
- Nominal field voltage: 24 VDC; operating range 18 VDC ~ 32 VDC
- Channel input current: 6.4 mA per channel
- Channel protection: Individual TR5 series 50 mA plug‑in fuse for each channel; field‑side short‑circuit only blows corresponding single‑channel fuse, no impact to other channels
- FTA power consumption: Passive termination assembly, no active on‑board power consumption
- Insulation: 500 VDC isolation, insulation resistance>100 MΩ
- Terminal wire gauge: 12 AWG ~ 24 AWG
- On‑board indicator LED: Field power supply status LED
- Dual redundant 24 VDC field power input with diode OR‑ing circuit
3. Environmental Conditions
- Operating temperature: 0 ℃ ~ +60 ℃
- Storage temperature: ‑20 ℃ ~ +70 ℃
- Relative humidity: 5 % ~ 95 % RH, non‑condensing
- Enclosure rating: IP20 (cabinet‑mount installation only, not for direct hazardous‑area mounting)
- Approvals: IEC 61508 SIL‑3 system compatible, ATEX, IECEx, UL, CE certified
- Conformal coating: Not available. For offshore high‑salt‑mist projects, select conformal‑coated I/O module T8403C while keeping standard T8800 FTA.
4. Main Functions
- 40‑channel field signal termination: Accept two‑wire 24 VDC discrete signals from field switches, pressure switches, level switches, smoke detectors, flame detectors and manual call‑points, interface to T8403 DI module.
- Per‑channel independent fuse protection: Isolates field short‑circuit faults, protects T8403 I/O module hardware.
- SmartSlot hot‑swap architecture: Back‑plane dual‑96‑way connector allows replacement of T8403 module without disconnecting field wiring.
- Dual 24 VDC field power input with diode redundancy for improved power availability.
- Power‑status LED for quick field‑supply troubleshooting.
- Fully compatible with TMR 2‑out‑of‑3 safety architecture for ESD emergency shutdown and Fire&Gas safety loops.
5. Typical Applications
- On‑shore and offshore platform SIS‑ESD emergency shutdown system for discrete digital input signal acquisition.
- Fire & Gas safety system: interface for flame detectors, smoke sensors, manual fire‑alarm call‑points, pressure / level switch contacts.
- Must only pair with T8403 / T8403C digital‑input module; incompatible with DO output modules.
Reference of Trusted T88xx series FTA|FTA Part No.|Function|Matched I/O Module|
|—|—|—|
|T8800|40‑Ch Digital Input FTA|T8403 / T8403C|
|T8842|40‑Ch Configurable DI/DO FTA|T8448 / T8448C|
|T8850|40‑Ch High‑current DO FTA|T8451 / T8451C|
|T8861|40‑Ch 24/48 VDC DO FTA|T8461 / T8461C|
6. Important Notes
- T8800 FTA itself has no conformal‑coated C‑version. For offshore projects use T8403C (conformal coated I/O card) with standard T8800 FTA.
- Strictly compatible only with T8403 / T8403C 40‑channel DI module; do not mate with other model I/O modules.
- Blown channel fuses must be replaced with TR5‑series 50 mA fuses.
- Install inside certified control cabinet on DIN‑rail; cannot be mounted directly within hazardous zone.
- Field 24 VDC power shall be provided externally for two‑wire input loops.